background image

10

Proper Piping Practice 

NOTE: The unit gas supply entrance is factory 

sealed with plugs. Keep plugs in place until 

gas supply is ready to be installed. Once ready, 

replace the plugs with the supplied grommets and 

install gas supply line.

Gas Piping Checks

WARNING

To prevent property damage or personal injury due to fire, 

the following instructions must be performed regarding 

gas connections and pressure testing:

• 

The unit and its gas connections must be leak tested 

before fire, never use a match or open flame to test 

for leaks. Never exceed specified pressures for 

testing. Higher pressure may damage gas valve and 

cause overfiring which may result in premature heat 

exchanger failure. 

• 

This unit and its shut-off valve must be disconnected 

from the gas supply during any pressure testing of that 

system at pressures in excess of 1/2 PSIG (3.48 kPA).

• 

This unit must be isolated from the gas supply system by 

closing its manual shut-off valve during any pressure 

testing of the gas supply piping system at test pressures 

equal to or less than 1/2 PSIG (3.48 kPA).

WARNING

To avoid property damage or personal injury, be sure there is 

no open flame in the vicinity during air bleeding.

There will be air in the gas supply line after testing for leaks 

on a new installation. Therefore, the air must be bled from 

the line by loosening the ground joint union until pure gas 

is expelled. Tighten union and wait for five minutes until all 

gas has been dissipated in the air. Be certain there is no 

open flame in the vicinity during air bleeding procedure. 

The unit is placed in operation by closing the main electrical 

disconnect switch for the unit.

ELECTRICAL WIRING

Thermostat Location

Mount the thermostat approximately five feet above the 

floor, in an area that has an inside, vibration-free wall  and 

has good air circulation.

Movement of air must not be obstructed by furniture, door, 

draperies, etc. The thermostat must not be mounted where 

it will be affected by drafts, hot or cold water pipes or air 

ducts in walls, radiant heat from fireplace, lamps, the sun, 

television, etc. Consult the Instruction Sheet packaged with 

thermostat for mounting instructions.

NOTE: All units have one stage of heating and 

either one or two stages of mechanical cooling. 

If the unit has two stages of mechanical cooling, 

the thermostat must also be two stage. Refer to 

figures later in this section for wiring.

WARNING

To avoid personal injury, electrical shock or death, 

disconnect electrical power before servicing or changing 

any electrical wiring.

The units are designed for operation on 60 hertz current 

and at voltages as shown on the rating plate. All internal 

wiring in the unit is complete. It is necessary to bring in the 

power supply to the contactor as shown on the unit wiring 

diagram which is supplied with each unit. The low voltage 

wiring must be connected between the unit control panel 

and the room thermostat.

R

C

G

W

Y

THERMOSTAT

RD

BL

GR WH YL YL

1 STAGE COOLING - 1 PHASE POWER

R

C

G

RD

BL

GR WH

W1 W2

Y1

Y2

YL YL

PU

PU

THERMOSTAT

2 STAGE COOLING - 1 PHASE POWER

WIRING LEGEND

FACTORY WIRING

FIELD WIRING

WIRE NUT CONNECTION

Refer to the unit wiring diagram for electrical connections. 

When installed, the unit must be electrically grounded in 

accordance with local codes or in the absence of local 

codes, with the National Electrical Code, ANSI/NFPA No. 

70, and/or the CSA C22.1 Electrical Code. Ensure low 

voltage connections are waterproof.

WARNING

To avoid the risk of electrical shock, wiring to the unit must 

be polarized and grounded.

Summary of Contents for A/GPU14 M Series

Page 1: ...Please contact your distributor or our website for the applicable Specification Sheets referred to in this manual This Forced Air Central Unit Design Complies With Requirements Embodied In The America...

Page 2: ...djustments 16 EEM Motors 16 Limit Check 17 Unit Shut Down 17 Compression Protection Devices 17 Refrigerant Charge Check 17 Cooling Refrigerant Charging Models with TXV 17 Superheat Adjustment 17 Cooli...

Page 3: ...seated and attached with the PCB or else the unit might not function as intended ID Plug PCB Terminal J9 Adjusting Gas Manifold Pressure Use the below manifold pressure settings Gas Input BTU HR Manif...

Page 4: ...uilding Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must b...

Page 5: ...n est n cessaire pour viter le danger d intoxica on au CO pouvant survenir si un appareil produisant du monoxyde de carbone con nue de fonc onner au sein de la zone confin e Esta ven laci n es necesar...

Page 6: ...n monoxide poisoning or death The following steps shall be followed with each appliance connected to the venting system placed in operation while any other appliances connected to the venting system a...

Page 7: ...observed when installing the unit IMPORTANT NOTE Remove wood shipping rails prior to installation of the unit All Installations For proper flame pattern within the heat exchanger and proper condensate...

Page 8: ...constructed using industry guidelines The duct work must be placed into the roof curb before mounting the package unit Curb insulation cant strips flashing and general roofing material are furnished b...

Page 9: ...400 610 70 46 96 180 370 560 80 43 90 170 350 530 90 40 84 160 320 490 100 38 79 150 305 460 Pressure 50 PSIG or less and Pressure Drop of 0 3 W C Based on 0 60 Specific Gravity Gas Natural Gas Capac...

Page 10: ...ermostat Location Mount the thermostat approximately five feet above the floor in an area that has an inside vibration free wall and has good air circulation Movement of air must not be obstructed by...

Page 11: ...30 35 40 45 50 SUPPLY WIRE LENGTH FEET 200 6 4 4 4 3 3 2 2 150 8 6 6 4 4 4 3 3 100 10 8 8 6 6 6 4 4 50 14 12 10 10 8 8 6 6 Wiring Table CIRCULATING AIR AND FILTERS Airflow Conversion Units can easily...

Page 12: ...All units may be externally filtered Refer to the unit filter size chart in the appendix for filter size information Filters installed external to the unit should be sized in accordance with their man...

Page 13: ...tisfied 5 The compressor and outdoor fan will be de energized when the thermostat opens 6 The indoor blower continues to run at low cool speed for approximately 60 seconds after the thermostat is sati...

Page 14: ...be as specified on the unit rating plate with all other household gas fired appliances operating The line pressure supplied to the gas valve must be within the Inlet Gas Supply Pressure range specifie...

Page 15: ...ressure tap 5 Turn ON the gas supply 6 Turn ON power and close thermostat R and W contacts to provide a call for heat 7 Using a leak detection solution or soap suds check for leaks at outlet pressure...

Page 16: ...give the correct air temperature rise through the unit as marked on the rating plate External Static Pressure Check The total external static pressure must be checked on this unit to determine if the...

Page 17: ...ect electrical power before inspecting or servicing the unit NOTE All compressor protection devices reset automatically energizing the contactor and outdoor fan WARNING Do not bypass safety devices Re...

Page 18: ...Record the gauge pressure and the temperature of the line 4 Compare the hi pressure reading to the Required Liquid Line Temperature chart Find the hi pressure value on the left column Follow that line...

Page 19: ...is outside the acceptable range for the null value the control enters a five minute lockout After the lockout timer has expired the control resumes normal operation During inducer operation including...

Page 20: ...nlet and flue outlet hoods are not blocked by debris which would prevent adequate combustion air and a properly operating vent system Filter Replacement or Cleaning A return air filter is not supplied...

Page 21: ...ormation on the yearly inspection consult the User Manual It is recommended that a qualified servicer inspect and service the unit at least once each year Turn the unit on at the thermostat Wait a few...

Page 22: ...LASH RETRIES EXCEEDED RED 1 HOUR FIXED 10 FLASHES HIGH LIMIT SWITCH RECOVERY TIMER EXPIRED RED 1 HOUR OR HARD LOCKOUT RAPID FLASH CLEAR ERROR HISTORY GREEN N A 2 FLASHES PRESSURE SENSOR NULL ERROR RED...

Page 23: ...U1442 M41 47 51 40 42 1 2 Large A GPU1448 M41 47 51 40 42 1 2 Large A GPU1461 M41 47 51 40 42 1 2 Large Model Unit Dimensions Inches Height Chassis Size W H W H A GPU1424 M41 16 16 16 16 A GPU1430 M41...

Page 24: ...PRIMARY LIMIT SWITCH RC RUN CAPACITOR TON ON DELAY TIMER RELAY TR TRANSFORMER VM VENT MOTOR WIRE CODE BLACK BLUE BROWN GREEN GRAY ORANGE PINK PURPLE RED TAN WHITE YELLOW BK BL BR GR GY OR PK PU RD TN...

Page 25: ...2 R2 PU 3 5 4 3 2 1 YL GR LINE VOLTAGE 208 230V 1PH 60Hz R C RD L1 L2 G R W Y C 5 4 3 2 1 GR COM TR BR RD BK RD YL OR BR WH BK OR YL BR 1 2 BK WH VM GR GR GR BL BL HPS LPS PU R C G Y2 Y1 W1 1 TO THERM...

Page 26: ...instructions D gaugement conforme aux codes d installation locaux aux exigences du fournisseur de gaz et aux instructions d installation du fabricant NOTE Roof overhang should be no more than 36 RECO...

Page 27: ...38 41 502 159 X 773 237 1011 324 0 8 444 165 828 245 42 444 165 X 690 245 948 329 PU1430060M41 Rise Range 30 60 E S P T1 FAN ONLY SPEED T2 HEATING SPEED T3 HEATING SPEED T4 COOLING SPEED T5 COOLING SP...

Page 28: ...677 0 7 644 196 966 305 52 899 278 56 1451 550 1629 686 0 8 587 206 901 315 54 832 285 59 1397 556 1578 693 PU1448080M41 Rise Range 30 60 E S P T1 FAN ONLY SPEED T2 HEATING SPEED T3 HEATING SPEED T4 C...

Page 29: ...ssor motor is hermetically sealed and does not require additional oiling Annual Inspection Qualified Servicer Only Your package unit should be inspected by a qualified installer or service agency at l...

Page 30: ...iquid Propane Residential Package Outdoor Section ELECTRICAL Supply Voltage Measure L1 and L2 Voltage L1 L2 Compressor Amps Condenser Fan Amps PRESSURES TEMPERATURES Suction Circuit Pressure Suction L...

Page 31: ...31 PAGE LEFT INTENTIONALLY BLANK...

Page 32: ...out us contact us You can also scan the QR code on the right for the product brand you purchased to be directed to the feedback page Our continuing commitment to quality products may mean a change in...

Reviews: