Amana A/GPU14 M Series Quick Start Manual Download Page 20

20

minutes. After this time elapses, the control evaluates the 

state of the blocked burner switch. If the switch is closed, 

the control resumes normal operation. The control will enter 

a one hour lockout state if the blocked burner switch fails to 

reset before the recovery timer has expired.

ID Plug

The control operational parameters are stored in ID Plug 

which connects on the circuit board. The control requires a 

valid ID plug present to operate in heating mode. If a valid 

ID plug is not present the control will not respond to a call 

for heat. However, the control will respond to thermostat 

inputs “Y” or “G”, operating the appropriate fan output. 

The cooling delays are ignored in this operating mode. 

The control puts the burner into hard lockout and will not 

respond to heating requests until the power is cycled with a 

valid ID plug installed.

Abnormal Operation - Cooling 

 

Short Cycle Compressor Delay

In the event of intermittent power losses or intermittent 

thermostat operation, the control system will delay output 

to the compressor contactor for three minutes from the time 

power is restored or thermostat call for cooling is restored.  

(Compressor is off a total of three minutes).

  

NOTE: Some electronic thermostats also have a 

built-in compressor short cycle timer that may be 

longer than the three minute delay given above.  

If you are using an electronic thermostat and the 

compressor has not started after three minutes, 

wait an additional five minutes to allow the 

thermostat to complete its short cycle delay time.

High Pressure Switch/Low Pressure Switch

Some models include a high pressure cutout switch and/

or a low pressure switch. The high pressure cutout switch 

protects the refrigeration system from excessive operating 

pressures. The low pressure switch protects the refriger-

ation system from very low operating pressures due to a 

loss of refrigerant. Compressor operation will be disabled if 

either of these devices opens. 

MAINTENANCE

WARNING

HIGH VOLTAGE

Disconnect ALL power before servicing or 

installing this unit. Multiple power sources 

may be present. Failure to do so may cause 

property damage, personal injury or death.

Have the gas heating section of the unit checked at least 

once a year before the heating season begins, to be sure 

that the combustion air inlet and flue outlet hoods are 

not blocked by debris, which would prevent adequate 

combustion air and a properly operating vent system.

Filter Replacement or Cleaning 

A return air filter is not supplied with this unit; however, 

there must be a means of filtering all of the return air. The 

filter(s) may be located in the return air duct(s), or return 

air filter grille(s). Consult with your installing dealer for the 

actual location of the return air filter(s) for your unit.

Dirty filters are the most common cause of inadequate 

heating or cooling performance. Filter inspection should be 

made at least every two months; more often if necessary 

because of local conditions and usage.

Dirty throwaway filters should be discarded and replaced 

with a new, clean filter. Dirty permanent filters should be 

washed with water, thoroughly dried and sprayed with a 

filter adhesive before being reinstalled (Filter adhesives 

may be found at many hardware stores). Permanent filters 

should last several years. However, should one become 

torn or uncleanable, it should be replaced.

Cabinet Finish Maintenance

Use a fine grade automotive wax on the cabinet finish to 

maintain the finish’s original high luster. This is especially 

important in installations with extended periods of direct 

sunlight.

Clean Outside Coil (Qualified Servicer Only)

The coil with the outside air flowing over it should be 

inspected annually and cleaned as frequently as necessary 

to keep the finned areas free of lint, hair and debris.

Condenser, Evaporator, and Induced Draft Motors 

Bearings on the air circulating blower motor, condenser 

motor and the combustion fan motor are permanently 

lubricated. No additional oiling is required.

Flame Sensor (Qualified Servicer Only)

A drop in the flame current can be caused by a nearly 

invisible coating on the flame sensor. This coating, created 

by the fuel or combustion air supply, can be removed by 

carefully cleaning the flame sensor with steel wool.

NOTE: After cleaning, the microamp signal should 

be stable and in the range of 5-10 microamps DC.

Flue Passages (Qualified Servicer Only)

At the start of each heating season, inspect and, if 

necessary, clean the unit flue passage.

Cleaning Flue Passages (Qualified Servicer Only)

1. 

Shut off electric power and gas supply to the unit. 

2.  Remove burner assembly by disconnecting the gas 

line and removing the manifold bracket from the 

partition panel.

3. 

Remove the flue from the induced draft blower and the 

collector box cover from the partition panel.

Summary of Contents for A/GPU14 M Series

Page 1: ...Please contact your distributor or our website for the applicable Specification Sheets referred to in this manual This Forced Air Central Unit Design Complies With Requirements Embodied In The America...

Page 2: ...djustments 16 EEM Motors 16 Limit Check 17 Unit Shut Down 17 Compression Protection Devices 17 Refrigerant Charge Check 17 Cooling Refrigerant Charging Models with TXV 17 Superheat Adjustment 17 Cooli...

Page 3: ...seated and attached with the PCB or else the unit might not function as intended ID Plug PCB Terminal J9 Adjusting Gas Manifold Pressure Use the below manifold pressure settings Gas Input BTU HR Manif...

Page 4: ...uilding Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must b...

Page 5: ...n est n cessaire pour viter le danger d intoxica on au CO pouvant survenir si un appareil produisant du monoxyde de carbone con nue de fonc onner au sein de la zone confin e Esta ven laci n es necesar...

Page 6: ...n monoxide poisoning or death The following steps shall be followed with each appliance connected to the venting system placed in operation while any other appliances connected to the venting system a...

Page 7: ...observed when installing the unit IMPORTANT NOTE Remove wood shipping rails prior to installation of the unit All Installations For proper flame pattern within the heat exchanger and proper condensate...

Page 8: ...constructed using industry guidelines The duct work must be placed into the roof curb before mounting the package unit Curb insulation cant strips flashing and general roofing material are furnished b...

Page 9: ...400 610 70 46 96 180 370 560 80 43 90 170 350 530 90 40 84 160 320 490 100 38 79 150 305 460 Pressure 50 PSIG or less and Pressure Drop of 0 3 W C Based on 0 60 Specific Gravity Gas Natural Gas Capac...

Page 10: ...ermostat Location Mount the thermostat approximately five feet above the floor in an area that has an inside vibration free wall and has good air circulation Movement of air must not be obstructed by...

Page 11: ...30 35 40 45 50 SUPPLY WIRE LENGTH FEET 200 6 4 4 4 3 3 2 2 150 8 6 6 4 4 4 3 3 100 10 8 8 6 6 6 4 4 50 14 12 10 10 8 8 6 6 Wiring Table CIRCULATING AIR AND FILTERS Airflow Conversion Units can easily...

Page 12: ...All units may be externally filtered Refer to the unit filter size chart in the appendix for filter size information Filters installed external to the unit should be sized in accordance with their man...

Page 13: ...tisfied 5 The compressor and outdoor fan will be de energized when the thermostat opens 6 The indoor blower continues to run at low cool speed for approximately 60 seconds after the thermostat is sati...

Page 14: ...be as specified on the unit rating plate with all other household gas fired appliances operating The line pressure supplied to the gas valve must be within the Inlet Gas Supply Pressure range specifie...

Page 15: ...ressure tap 5 Turn ON the gas supply 6 Turn ON power and close thermostat R and W contacts to provide a call for heat 7 Using a leak detection solution or soap suds check for leaks at outlet pressure...

Page 16: ...give the correct air temperature rise through the unit as marked on the rating plate External Static Pressure Check The total external static pressure must be checked on this unit to determine if the...

Page 17: ...ect electrical power before inspecting or servicing the unit NOTE All compressor protection devices reset automatically energizing the contactor and outdoor fan WARNING Do not bypass safety devices Re...

Page 18: ...Record the gauge pressure and the temperature of the line 4 Compare the hi pressure reading to the Required Liquid Line Temperature chart Find the hi pressure value on the left column Follow that line...

Page 19: ...is outside the acceptable range for the null value the control enters a five minute lockout After the lockout timer has expired the control resumes normal operation During inducer operation including...

Page 20: ...nlet and flue outlet hoods are not blocked by debris which would prevent adequate combustion air and a properly operating vent system Filter Replacement or Cleaning A return air filter is not supplied...

Page 21: ...ormation on the yearly inspection consult the User Manual It is recommended that a qualified servicer inspect and service the unit at least once each year Turn the unit on at the thermostat Wait a few...

Page 22: ...LASH RETRIES EXCEEDED RED 1 HOUR FIXED 10 FLASHES HIGH LIMIT SWITCH RECOVERY TIMER EXPIRED RED 1 HOUR OR HARD LOCKOUT RAPID FLASH CLEAR ERROR HISTORY GREEN N A 2 FLASHES PRESSURE SENSOR NULL ERROR RED...

Page 23: ...U1442 M41 47 51 40 42 1 2 Large A GPU1448 M41 47 51 40 42 1 2 Large A GPU1461 M41 47 51 40 42 1 2 Large Model Unit Dimensions Inches Height Chassis Size W H W H A GPU1424 M41 16 16 16 16 A GPU1430 M41...

Page 24: ...PRIMARY LIMIT SWITCH RC RUN CAPACITOR TON ON DELAY TIMER RELAY TR TRANSFORMER VM VENT MOTOR WIRE CODE BLACK BLUE BROWN GREEN GRAY ORANGE PINK PURPLE RED TAN WHITE YELLOW BK BL BR GR GY OR PK PU RD TN...

Page 25: ...2 R2 PU 3 5 4 3 2 1 YL GR LINE VOLTAGE 208 230V 1PH 60Hz R C RD L1 L2 G R W Y C 5 4 3 2 1 GR COM TR BR RD BK RD YL OR BR WH BK OR YL BR 1 2 BK WH VM GR GR GR BL BL HPS LPS PU R C G Y2 Y1 W1 1 TO THERM...

Page 26: ...instructions D gaugement conforme aux codes d installation locaux aux exigences du fournisseur de gaz et aux instructions d installation du fabricant NOTE Roof overhang should be no more than 36 RECO...

Page 27: ...38 41 502 159 X 773 237 1011 324 0 8 444 165 828 245 42 444 165 X 690 245 948 329 PU1430060M41 Rise Range 30 60 E S P T1 FAN ONLY SPEED T2 HEATING SPEED T3 HEATING SPEED T4 COOLING SPEED T5 COOLING SP...

Page 28: ...677 0 7 644 196 966 305 52 899 278 56 1451 550 1629 686 0 8 587 206 901 315 54 832 285 59 1397 556 1578 693 PU1448080M41 Rise Range 30 60 E S P T1 FAN ONLY SPEED T2 HEATING SPEED T3 HEATING SPEED T4 C...

Page 29: ...ssor motor is hermetically sealed and does not require additional oiling Annual Inspection Qualified Servicer Only Your package unit should be inspected by a qualified installer or service agency at l...

Page 30: ...iquid Propane Residential Package Outdoor Section ELECTRICAL Supply Voltage Measure L1 and L2 Voltage L1 L2 Compressor Amps Condenser Fan Amps PRESSURES TEMPERATURES Suction Circuit Pressure Suction L...

Page 31: ...31 PAGE LEFT INTENTIONALLY BLANK...

Page 32: ...out us contact us You can also scan the QR code on the right for the product brand you purchased to be directed to the feedback page Our continuing commitment to quality products may mean a change in...

Reviews: