background image

 

ReServWP 

- 3 -

Installation Instructions:

This installation should be made by qualified service personnel and should conform to all local codes and in 
accordance with the National Electrical Code. This product contains no serviceable parts.
1.  Remove back plate inside the enclosure by removing four (4) mounting screws and ground lug. 
 

Do not discard hardware.

2.  Mark and drill desired knockouts on the enclosure to facilitate wiring.
 

Note: It is required to use UL Listed outdoor rated conduit hubs with a minimum outdoor rating of 4X.

3.  Secure back plate and ground lug inside the enclosure with four (4) mounting screws (Figs. 1-2, pg. 5-6).
4.  Mount unit in the desired location with the appropriate fasteners utilizing the holes provided on the 
 

enclosure’s flanges (Pgs. 7 and 8). Secure enclosure to earth ground. 

 

Note: This product needs to be secured to the building/pole before operation.

5.  Connect AC power mains to the terminals marked [L] and [N] (Figs. 1-2, pg. 5-6).
 

Use 18 AWG or larger for all power connections (Battery, output) (Figs. 1-2, pg. 5-6).

 

Use 18 AWG to 22 AWG for power-limited circuits (AC Fail/Low Battery reporting) (Figs. 1-2, pg. 5-6).

 

Note: A readily accessible disconnect device shall be incorporated in the building installation wiring.

 

Keep power-limited wiring separate from non power-limited wiring 

 

(115VAC 60Hz Input, Battery Wires). Minimum 0.25” spacing must be provided. 

 

CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or 

 

servicing equipment. There are no user serviceable parts inside. 

 

Refer installation and servicing to qualified service personnel. 

6.  The LEDs on the power supply board will illuminate when AC power is present.
7.  Measure output voltage before connecting cameras/devices to outputs. This helps avoiding potential damage.
8.  ReServ3WP only - Adjust voltage for every two (2) outputs using the corresponding trimpot(s) on the 
 

board prior to connecting devices.

9.  Connecting cameras/devices:
 

ReServ1WP: 

Connect 12VDC cameras/devices to the terminals marked [P 1-4], [N 1-4] (Fig. 1, pg. 5).

 

 

   

Connect 24VAC cameras/devices to the terminals marked [5-16] (Fig. 1, pg. 5).

 

ReServ2WP: 

Connect 24VAC cameras/devices to the terminals marked [1-16] (Fig. 1, pg. 5).

 

ReServ3WP: 

Connect 12VDC cameras/devices to the terminals marked [P 1-16], [N 1-16] (Fig. 2, pg. 6).

10.  Connect batteries to the terminals marked [+ BAT –] (Figs. 1-2, pg. 5-6)
 

Use two (2) 12VDC batteries connected in series for 24VDC operation (battery leads included).

 

Use batteries - Casil CA1270 (12V/7AH), Genesis NP7-12 (12V/7AH) or NP7-12 (12V/12AH), 

 

Ultratech UT1270 (12V/7AH) or Ultratech UT12120 (12V/12AH).

11.  Connect appropriate signaling notification devices to AC FAIL and BAT FAIL (Figs. 1-2, pg. 5-6) 
 

supervisory relay outputs.

12.  The power LEDs on the unit for Outputs 1-16 will illuminate when AC power is present (Figs. 1-2, pg. 5-6)
 

Note: If any of the power LEDs are not illuminated the cause may be due to the following:

 

a.  AC mains and battery fail.

 

b.  One (1) or more power output PTCs are tripped due to a short circuit or overload condition.

 

c.  Unit damaged/defective.

 

 

To reset the PTC:

 

 

1.  Disconnect corresponding camera/device connected to terminals marked [1-16] (Figs. 1-2, pg. 5-6).

 

 

2.  Eliminate the trouble condition (short circuit or overload).

 

 

3.  Allow 1 minute for PTC to cool off (reset).

 

 

4.  Connect corresponding cameras/devices to terminals marked [1-16] (Figs. 1-2, pg. 5-6).

 

 

5.  Power LEDs will illuminate indicating power has been restored to outputs (Figs. 1-2, pg. 5-6).

WARNING: This installation should be made by qualified service personnel and should 

conform to the National Electrical Code and all local codes.

The lightning flash with arrow head symbol within an equilateral triangle is intended to alert the 
user to the presence of an insulated DANGEROUS VOLTAGE within the product’s enclosure that 
may be of sufficient magnitude to constitute an electric shock.

The exclamation point within an equilateral triangle is intended to alert the user to the presence of 
important operating and maintenance (servicing) instructions in the literature accompanying
the appliance.

CAUTION: To reduce the risk of electric shock do not open enclosure. 
There are no user serviceable parts inside. Refer servicing to qualified 
service personnel.

Summary of Contents for ReServ1WP

Page 1: ... and Four 4 regulated 12VDC outputs 4A total supply current 24VAC and 2A total supply current 12VDC PTC protected power limited outputs ReServ2WP Sixteen 16 true sine wave regulated 24VAC outputs 4A total supply current PTC protected power limited outputs ReServ3WP Sixteen 16 regulated 12VDC outputs 8A total supply current PTC protected power limited outputs ...

Page 2: ...pecifications Output PTC protected power limited outputs are rated 1A Battery Backup Built in charger for sealed lead acid or gel type batteries Automatic switchover to stand by battery when AC fails Supervision AC fail supervision form C contacts Low battery supervision form C contacts Visual and Audio Indicators AC DC power LED indicators Individual power output LED indicators Low voltage input ...

Page 3: ...minals marked P 1 4 N 1 4 Fig 1 pg 5 Connect 24VAC cameras devices to the terminals marked 5 16 Fig 1 pg 5 ReServ2WP Connect 24VAC cameras devices to the terminals marked 1 16 Fig 1 pg 5 ReServ3WP Connect 12VDC cameras devices to the terminals marked P 1 16 N 1 16 Fig 2 pg 6 10 Connect batteries to the terminals marked BAT Figs 1 2 pg 5 6 Use two 2 12VDC batteries connected in series for 24VDC ope...

Page 4: ...ery Terminal Identification Power Supply Board Terminal Legend Function Description L G N Connect 115VAC 60Hz to these terminals L to hot N to neutral DC 24VDC non power limited output AC FAIL NO C NC Form C dry contacts used to instantaneously signal the loss AC to local annunciation devices With AC present terminals marked NO and C are open NC and C are closed When loss of AC occurs terminals ma...

Page 5: ...of used batteires according to the instructions 12VDC Rechargeable Battery order separately Note Two 2 12VDC rechargeable batteries connected in series required Supervised Non power limited Unswitched 115VAC 60Hz 3 5A power mains non power limited Green Lead L G N BAT DC NC C NO NC C NO Input 24VDC power limited Non power limited ...

Page 6: ...rechargeable batteries connected in series required Supervised Non power limited Unswitched 115VAC 60Hz 3 5A power mains non power limited L G N BAT DC NC C NO NC C NO power limited Non power limited 12VDC Power Limited Outputs 24VDC P N 1 OUT 2 1 2V adjust P N 3 OUT 4 3 4V adjust P N 5 OUT 6 5 6V adjust P N 7 OUT 8 7 8V adjust P N 9 OUT 10 9 10V adjust P N 11 OUT 12 11 12V adjust P N 13 OUT 14 13...

Page 7: ...op Pole Mount bracket is achieved tighten the straps down by sliding open end of the strap through the locking mechanism on the strap then tighten the screw with flat head screwdriver or 5 16 hex socket driver Fig 5 pg 7 and Fig 7 pg 7 3 Attach the bottom bracket to the enclosure by inserting bolts through the flange of the enclosure and into the bracket tightening bolts with a 7 16 hex socket Fig...

Page 8: ...17 53 x 15 3 x 6 67 445 3mm x 388 6mm x 169 4mm FRONT VIEW COVER REMOVED RIGHT SIDE VIEW FRONT VIEW END VIEW SECTION A A A A 316 STAINLESS STEEL PADLOCK LATCH ATTACHED WITH RIVETS Ø 375 PADLOCK EYE 17 36 441 mm 12 00 304 8mm 6 41 162 8mm 10 32 X 250 BRASS INSERT 4 PLCS 14 54 369 3mm 16 74 425 2mm 0 125 3 2mm 14 25 362mm 14 00 355 6mm 12 23 310 6mm 17 53 445 3mm 16 00 406 4mm 1 67 42 4mm 5 00 127mm...

Reviews: