Application Notes
P54x/EN AP/La4
MiCOM P543, P544, P545 & P546
(AP) 6-19
AP
In the case of high resistance external faults on a short line, particularly under heavy power
exporting conditions, zone 1 will remain stable due to dynamic downwards tilting of the top
line as explained earlier but the detection of high resistance internal faults especially towards
the end of the line needs consideration. In such applications a user has a choice to either
detect high resistance faults using highly sensitive Aided DEF or Delta Directional schemes
or to clear the fault with distance ground protection. If distance is to operate, it is necessary
to eliminate over-tilting for internal faults by reducing the initial -3° tilting angle to zero so that
the overall top line tilt will equal to (Iph-I2) angle only.
As per Figure 4, the internal resistive fault will then fall in the zone 1 operating characteristic.
However, it should be noted that for short lines the load angle is relatively low when
compared to long transmission lines for the same transfer capacity and therefore the top line
dynamic tilting may be moderate. Therefore it may be necessary to reduce the zone one
reach to guarantee zone 1 stability. This is particularly recommended if distance is operating
in an aided scheme. To summarize, for very short lines with large R/X setting ratios, it is
recommended to set the initial tilt angle to zero and zone 1 reach to 70-75% of the line
impedance.
Note:
The above discussion assumes homogenous networks where the
angle of the negative sequence current derived at relaying point is
very close to the total fault current angle. If the network is non-
homogenous, there will be a difference in angle that will cause
inaccurate dynamic tilting, hence in such networks either quad with
fixed tilt angle or even Mho characteristic should be considered in
order to avoid zone 1 over-reach.
Fixed tilt angle:
As an alternative to Dynamic tilting, a user can set a fixed tilt angle. This is applicable to
applications where the power flow direction is unidirectional.
Exporting end:
To secure stability, the tilt angle of zone 1 at exporting end has to be set negative and above
the maximum angle difference between sources feeding the resistive faults. This data
should be known from load flow study, but if unavailable, the minimum recommended setting
would be the angle difference between voltage and current measured at local end during the
heaviest load condition coupled with reduced zone 1 reach of 70-75% of the line impedance.
Note:
Figure 4 shows that at sharp fixed tilt angle, the effective resistive
coverage would be significantly reduced, and therefore for the short
lines the dynamic tilting (with variable tilt angle depending on fault
resistance and location) is preferred. For all other over-reaching
zones set tilting angle to zero.
Importing end:
Set zone 1 tilt angle to zero and for all other zones the typical setting should be positive and
b(5-10)°.
Note:
The setting accuracy for over-reaching zones is not crucial because it
will not pose a risk for relay’s maloperation, the purpose is only to
boost zone 2 and zone 4 reach and improve distance aided schemes.
Summary of Contents for MiCOM P54 Series
Page 2: ......
Page 4: ......
Page 5: ...Safety Section P54x EN SS H11 SS SAFETY SECTION...
Page 6: ...P54x EN SS H11 Safety Section SS...
Page 8: ...P54x EN SS H11 Safety Section SS 2 SS...
Page 16: ...P54x EN IT La4 Introduction MiCOM P543 P544 P545 P546 IT...
Page 18: ...P54x EN IT La4 Introduction IT 1 2 MiCOM P543 P544 P545 P546 IT...
Page 28: ...P54x EN IT La4 Introduction IT 1 12 MiCOM P543 P544 P545 P546 IT...
Page 30: ...P54x EN TD La4 Technical Data MiCOM P543 P544 P545 P546 TD...
Page 58: ...P54x EN GS La4 Getting Started MiCOM P543 P544 P545 P546 GS...
Page 78: ...P54x EN ST La4 Settings MiCOM P543 P544 P545 P546 ST...
Page 172: ...P54x EN ST La4 Settings ST 4 94 MiCOM P543 P544 P545 P546 ST...
Page 174: ...P54x EN OP La4 Operation MiCOM P543 P544 P545 P546 OP...
Page 442: ...P54x EN OP B94 Operation OP 5 270 MiCOM P543 P544 P545 P546 OP...
Page 444: ...P54x EN AP La4 Application Notes MiCOM P543 P544 P545 P546 AP...
Page 534: ...P54x EN PL La4 Programmable Logic MiCOM P543 P544 P545 P546 PL...
Page 538: ...P54x EN PL La4 Programmable Logic PL 7 4 MiCOM P543 P544 P545 P546 PL...
Page 602: ...P54x EN PL La4 Programmable Logic PL 7 68 MiCOM P543 P544 P545 P546 Output Contacts PL...
Page 603: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 69 Output Contacts PL...
Page 606: ...P54x EN PL La4 Programmable Logic PL 7 72 MiCOM P543 P544 P545 P546 PL...
Page 616: ...P54x EN PL La4 Programmable Logic PL 7 82 MiCOM P543 P544 P545 P546 Output Contacts PL...
Page 619: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 85 PL...
Page 620: ...P54x EN PL La4 Programmable Logic PL 7 86 MiCOM P543 P544 P545 P546 PL...
Page 621: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 87 PL...
Page 624: ...P54x EN PL La4 Programmable Logic PL 7 90 MiCOM P543 P544 P545 P546 PL...
Page 629: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 95 Output Contacts PL...
Page 630: ...P54x EN PL La4 Programmable Logic PL 7 96 MiCOM P543 P544 P545 P546 PL...
Page 631: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 97 PL...
Page 633: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 99 PL...
Page 637: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 103 PL...
Page 641: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 107 Output Contacts PL...
Page 642: ...P54x EN PL La4 Programmable Logic PL 7 108 MiCOM P543 P544 P545 P546 Output Contacts PL...
Page 643: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 109 LEDs PL...
Page 644: ...P54x EN PL La4 Programmable Logic PL 7 110 MiCOM P543 P544 P545 P546 PL...
Page 645: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 111 PL...
Page 647: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 113 PL...
Page 653: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 119 Output Contacts PL...
Page 655: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 121 Output Contacts PL...
Page 656: ...P54x EN PL La4 Programmable Logic PL 7 122 MiCOM P543 P544 P545 P546 LEDs PL...
Page 663: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 129 PL...
Page 667: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 133 Output Contacts PL...
Page 669: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 135 Output Contacts PL...
Page 671: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 137 PL...
Page 672: ...P54x EN PL La4 Programmable Logic PL 7 138 MiCOM P543 P544 P545 P546 PL...
Page 676: ...P54x EN PL La4 Programmable Logic PL 7 142 MiCOM P543 P544 P545 P546 PL...
Page 681: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 147 Output Contacts PL...
Page 688: ...P54x EN PL La4 Programmable Logic PL 7 154 MiCOM P543 P544 P545 P546 PL...
Page 689: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 155 PL...
Page 690: ...P54x EN PL La4 Programmable Logic PL 7 156 MiCOM P543 P544 P545 P546 PL...
Page 696: ...P54x EN PL La4 Programmable Logic PL 7 162 MiCOM P543 P544 P545 P546 Output Contacts PL...
Page 698: ...P54x EN PL La4 Programmable Logic PL 7 164 MiCOM P543 P544 P545 P546 PL...
Page 701: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 167 PL...
Page 703: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 169 PL...
Page 704: ...P54x EN PL La4 Programmable Logic PL 7 170 MiCOM P543 P544 P545 P546 PL...
Page 705: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 171 PL...
Page 706: ...P54x EN PL La4 Programmable Logic PL 7 172 MiCOM P543 P544 P545 P546 LEDs PL...
Page 708: ...P54x EN MR La4 Measurements and Recording MiCOM P543 P544 P545 P546 MR...
Page 710: ...P54x EN MR La4 Measurements and Recording MR 8 2 MiCOM P543 P544 P545 P546 MR...
Page 726: ...P54x EN FD La4 Firmware Design MiCOM P543 P544 P545 P546 FD...
Page 748: ...P54x EN CM La4 Commissioning MiCOM P543 P544 P545 P546 CM...
Page 754: ...P54x EN CM La4 Commissioning CM 10 6 MiCOM P543 P544 P545 P546 CM...
Page 874: ...P54x EN MT La4 Maintenance MiCOM P543 P544 P545 P546 MT MT...
Page 876: ...P54x EN MT La4 Maintenance MT 11 2 MiCOM P543 P544 P545 P546 MT...
Page 882: ...P54x EN TS La4 Troubleshooting MiCOM P543 P544 P545 P546 TS...
Page 884: ...P54x EN TS La4 Troubleshooting TS 12 2 MiCOM P543 P544 P545 P546 TS...
Page 894: ...P54x EN SC La4 SCADA Communications MiCOM P543 P544 P545 P546 SC...
Page 928: ...P54x EN SG La4 Symbols and Glossary MiCOM P543 P544 P545 P546 SG...
Page 938: ...P54x EN SG La4 Symbols and Glossary SG 14 10 MiCOM P543 P544 P545 P546 SG...
Page 940: ...P54x EN IN La4 Installation MiCOM P543 P544 P545 P546 IN...
Page 974: ...P54x EN IN La4 Installation IN 15 34 MiCOM P543 P544 P545 P546 IN...
Page 976: ...P54x EN VH La4 Firmware and Service Manual Version History MiCOM P543 P544 P545 P546 VH...
Page 1023: ......