P54x/EN OP/La4
Operation
(OP) 5-192
MiCOM P543, P544, P545 & P546
OP
Where L refers to the leader circuit breaker, F refers to the follower circuit breaker, 1P
implies single phase, 3P implies three phase, and 1/3P implies single or three phase, so a
setting of
L1/3P F3P
would mean that the leader circuit breaker could perform single or three
phase auto-reclose, whilst the follower would perform three phase auto-reclose only.
If the auto-reclose mode selection is by
Opto
then the reclose mode for the active leader is
determined by the status of two DDB inputs:
Lead AR 1P
(1497) to enable single phase
auto-reclose, and “
Lead AR 3P
” (1498) to enable three phase auto-reclose. The reclose
mode for the active follower is determined by the status of two DDB inputs:
Follower AR 1P
(1409) to enable single phase auto-reclose, and
Follower AR 3P
(1410) to enable three
phase auto-reclose.
Where the selected follower auto-reclose mode supports single phase tripping, the follower
can perform single phase auto-reclose only if the leader circuit breaker has performed single
phase auto-reclose. If the leader has tripped and reclosed three phase, the follower is also
forced to trip three phase. The follower will reclose three phase provided three phase auto-
reclose is permitted for the follower circuit breaker. If the follower circuit breaker trips three
phase and three phase auto-reclose is not permitted for the follower, then the follower circuit
breaker locks out without reclosing.
5.6.6.5 Force three phase trip
(P544/P546)
The
force three phase trip
logic is shown in AR Figure 10 (logic diagram supplement).
Following single phase tripping, whilst the auto-reclose cycle is in progress, and upon
resetting of the protection elements, an output signal DDB associated with the tripped circuit
breaker is asserted high.
In the case of CB1, this is DDB:
AR Force CB1 3P
(858).
In the case of CB2, this is DDB:
AR Force CB2 3P
(1485).
These signals are applied to any associated protection trip conversion logic to force all
protection trips to be converted to three phase trips for the associated circuit breaker, for any
subsequent faults that occur whilst the auto-reclose cycle remains in progress.
5.6.6.6 Auto-reclose Initiation
(P544/P546)
The auto-reclose initiation logic is shown in AR Figure 11, Figure 12, Figure 13 and
Figure 14 (logic diagram supplement).
Auto-reclose cycles can be initiated by :-
Protection functions hosted by the P544/P546
External protection equipment
Trip
test
Auto-reclose initiation will start an auto-reclose for any circuit breaker that is in service and
enabled for auto-reclose: CB1 auto-reclose will start if CB1 is in service and enabled for
auto-reclose; CB2 auto-reclose will start if CB2 is in service and enabled for auto-reclose.
When an auto-reclose cycle is started, the relevant circuit breaker auto-reclose in progress
CB1 ARIP
and/or
CB2 ARIP
signal is set, and remains set until the end of the cycle for the
associated circuit breaker. The end of the cycle is signified by successful reclosure, or by
lockout.
5.6.6.6.1 Auto-reclose initiation by host relay protection function (P544/P546)
Many protection functions in the P544/P546 (for example differential trips, Zone 1 trips,
distance-aided scheme trips, time-delayed distance zones, overcurrent and earth (ground)
elements, DEF and directional aided schemes.) can be programmed to initiate or block auto-
reclose by selecting the
Initiate AR
, or
Block AR
options in the settings which are available
under the
AUTORECLOSE
settings column of the menu. Operation of a protection function
selected for auto-reclose will initiate auto-reclose. Operation of a protection function
selected to block auto-reclose will block and force a lockout.
Summary of Contents for MiCOM P54 Series
Page 2: ......
Page 4: ......
Page 5: ...Safety Section P54x EN SS H11 SS SAFETY SECTION...
Page 6: ...P54x EN SS H11 Safety Section SS...
Page 8: ...P54x EN SS H11 Safety Section SS 2 SS...
Page 16: ...P54x EN IT La4 Introduction MiCOM P543 P544 P545 P546 IT...
Page 18: ...P54x EN IT La4 Introduction IT 1 2 MiCOM P543 P544 P545 P546 IT...
Page 28: ...P54x EN IT La4 Introduction IT 1 12 MiCOM P543 P544 P545 P546 IT...
Page 30: ...P54x EN TD La4 Technical Data MiCOM P543 P544 P545 P546 TD...
Page 58: ...P54x EN GS La4 Getting Started MiCOM P543 P544 P545 P546 GS...
Page 78: ...P54x EN ST La4 Settings MiCOM P543 P544 P545 P546 ST...
Page 172: ...P54x EN ST La4 Settings ST 4 94 MiCOM P543 P544 P545 P546 ST...
Page 174: ...P54x EN OP La4 Operation MiCOM P543 P544 P545 P546 OP...
Page 442: ...P54x EN OP B94 Operation OP 5 270 MiCOM P543 P544 P545 P546 OP...
Page 444: ...P54x EN AP La4 Application Notes MiCOM P543 P544 P545 P546 AP...
Page 534: ...P54x EN PL La4 Programmable Logic MiCOM P543 P544 P545 P546 PL...
Page 538: ...P54x EN PL La4 Programmable Logic PL 7 4 MiCOM P543 P544 P545 P546 PL...
Page 602: ...P54x EN PL La4 Programmable Logic PL 7 68 MiCOM P543 P544 P545 P546 Output Contacts PL...
Page 603: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 69 Output Contacts PL...
Page 606: ...P54x EN PL La4 Programmable Logic PL 7 72 MiCOM P543 P544 P545 P546 PL...
Page 616: ...P54x EN PL La4 Programmable Logic PL 7 82 MiCOM P543 P544 P545 P546 Output Contacts PL...
Page 619: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 85 PL...
Page 620: ...P54x EN PL La4 Programmable Logic PL 7 86 MiCOM P543 P544 P545 P546 PL...
Page 621: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 87 PL...
Page 624: ...P54x EN PL La4 Programmable Logic PL 7 90 MiCOM P543 P544 P545 P546 PL...
Page 629: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 95 Output Contacts PL...
Page 630: ...P54x EN PL La4 Programmable Logic PL 7 96 MiCOM P543 P544 P545 P546 PL...
Page 631: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 97 PL...
Page 633: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 99 PL...
Page 637: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 103 PL...
Page 641: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 107 Output Contacts PL...
Page 642: ...P54x EN PL La4 Programmable Logic PL 7 108 MiCOM P543 P544 P545 P546 Output Contacts PL...
Page 643: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 109 LEDs PL...
Page 644: ...P54x EN PL La4 Programmable Logic PL 7 110 MiCOM P543 P544 P545 P546 PL...
Page 645: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 111 PL...
Page 647: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 113 PL...
Page 653: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 119 Output Contacts PL...
Page 655: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 121 Output Contacts PL...
Page 656: ...P54x EN PL La4 Programmable Logic PL 7 122 MiCOM P543 P544 P545 P546 LEDs PL...
Page 663: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 129 PL...
Page 667: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 133 Output Contacts PL...
Page 669: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 135 Output Contacts PL...
Page 671: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 137 PL...
Page 672: ...P54x EN PL La4 Programmable Logic PL 7 138 MiCOM P543 P544 P545 P546 PL...
Page 676: ...P54x EN PL La4 Programmable Logic PL 7 142 MiCOM P543 P544 P545 P546 PL...
Page 681: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 147 Output Contacts PL...
Page 688: ...P54x EN PL La4 Programmable Logic PL 7 154 MiCOM P543 P544 P545 P546 PL...
Page 689: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 155 PL...
Page 690: ...P54x EN PL La4 Programmable Logic PL 7 156 MiCOM P543 P544 P545 P546 PL...
Page 696: ...P54x EN PL La4 Programmable Logic PL 7 162 MiCOM P543 P544 P545 P546 Output Contacts PL...
Page 698: ...P54x EN PL La4 Programmable Logic PL 7 164 MiCOM P543 P544 P545 P546 PL...
Page 701: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 167 PL...
Page 703: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 169 PL...
Page 704: ...P54x EN PL La4 Programmable Logic PL 7 170 MiCOM P543 P544 P545 P546 PL...
Page 705: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 171 PL...
Page 706: ...P54x EN PL La4 Programmable Logic PL 7 172 MiCOM P543 P544 P545 P546 LEDs PL...
Page 708: ...P54x EN MR La4 Measurements and Recording MiCOM P543 P544 P545 P546 MR...
Page 710: ...P54x EN MR La4 Measurements and Recording MR 8 2 MiCOM P543 P544 P545 P546 MR...
Page 726: ...P54x EN FD La4 Firmware Design MiCOM P543 P544 P545 P546 FD...
Page 748: ...P54x EN CM La4 Commissioning MiCOM P543 P544 P545 P546 CM...
Page 754: ...P54x EN CM La4 Commissioning CM 10 6 MiCOM P543 P544 P545 P546 CM...
Page 874: ...P54x EN MT La4 Maintenance MiCOM P543 P544 P545 P546 MT MT...
Page 876: ...P54x EN MT La4 Maintenance MT 11 2 MiCOM P543 P544 P545 P546 MT...
Page 882: ...P54x EN TS La4 Troubleshooting MiCOM P543 P544 P545 P546 TS...
Page 884: ...P54x EN TS La4 Troubleshooting TS 12 2 MiCOM P543 P544 P545 P546 TS...
Page 894: ...P54x EN SC La4 SCADA Communications MiCOM P543 P544 P545 P546 SC...
Page 928: ...P54x EN SG La4 Symbols and Glossary MiCOM P543 P544 P545 P546 SG...
Page 938: ...P54x EN SG La4 Symbols and Glossary SG 14 10 MiCOM P543 P544 P545 P546 SG...
Page 940: ...P54x EN IN La4 Installation MiCOM P543 P544 P545 P546 IN...
Page 974: ...P54x EN IN La4 Installation IN 15 34 MiCOM P543 P544 P545 P546 IN...
Page 976: ...P54x EN VH La4 Firmware and Service Manual Version History MiCOM P543 P544 P545 P546 VH...
Page 1023: ......