Operation
P54x/EN OP/La4
MiCOM P543, P544, P545 & P546
(OP) 5-185
OP
Following this introduction to the logic sequence, is a comprehensive description of the auto-
reclose and circuit breaker operation.
An auto-reclose cycle can be internally initiated by operation of a protection element,
provided the circuit breaker is closed until the instant of protection operation.
The operation of the auto-reclose sequence is controlled by the “Dead Timers”. The user
can, via settings, determine what conditions will be used to initiate the dead timers as
described in section 5.6.6.9. In general, however, and for the purposes of this description,
the dead timers can be considered to start upon initiation of the auto-reclose cycle by the
protection.
If only single phase auto-reclose
AR 1P
is enabled then the logic allows only a single shot
auto-reclose. For a single phase fault, the single phase dead timer
SP AR Dead Time
starts, and the single phase auto-reclose in progress signal
CB1 AR 1p InProg
(DDB 845)
is
asserted. For a multi-phase fault the logic triggers a three phase trip and goes to lockout.
If only three phase auto-reclose
AR 3P
is enabled then, for any fault, the three phase dead
timers:
3P AR DT Shot 1
,
3P AR DT Shot 2
,
3P AR DT Shot 3
,
3P AR DT Shot 4
, (Dead
Time 1, 2, 3, 4) are started and the three phase auto-reclose in progress signal
CB1 AR 3p InProg
(DDB 844) is asserted. The logic forces a three phase trip by setting
AR Force CB1 3P
(DDB 858) for any single phase fault if only three phase auto-reclose
AR 3P
is enabled.
If single and three phase auto-reclose
AR1/3P
are enabled then, if the first fault is a single
phase fault the single phase dead time
SP AR Dead Time
is started and the single phase
auto-reclose in progress signal
CB1 AR 1p InProg
(DDB 845) is asserted. If the first fault is
a multi-phase fault the three phase dead timer
3P AR DT Shot 1
is started and the three
phase auto-reclose in progress signal
CB1 AR 3p InProg
(DDB 844) is asserted. If the relay
has been set to allow more than one reclose (
AR Shots >1
) then any subsequent faults will
be converted to three phase trips by setting the signal
AR Force CB1 3P
(DDB 858). The
three phase dead times
3P AR DT Shot 2
,
3P AR DT Shot 3
and
3P AR DT Shot 4
(Dead
Times 2, 3, 4) will be started for the 2nd, 3rd and 4th trips (shots) respectively. The three
phase auto-reclose in progress signal
CB1 AR 3p InProg
(DDB 844) will be asserted. If a
single phase fault evolves to a multi-phase fault during the single phase dead time
(
SP AR Dead Time
) then single phase auto-reclose is stopped. The single phase
auto-reclose in progress signal
CB1 AR 1p InProg
(DDB 845) is reset, the three phase
auto-reclose in progress signal
CB1 AR 3p InProg
(DDB 844) is set, and the three phase
dead timer
3P AR DT Shot 1
is started.
At the end of the relevant dead time, provided system conditions are suitable, a circuit
breaker close signal is given. The system conditions to be met for closing are that the
system voltages are in synchronism or that the dead line/live bus or live line/dead bus
conditions exist, indicated by the internal system check synchronizing element, and that the
circuit breaker closing spring, or other energy source, is fully charged as indicated by the
CB Healthy
input. The circuit breaker close signal is cut-off when the circuit breaker closes.
For single phase auto-reclose no voltage or synchronism check is required as synchronizing
power is flowing in the two healthy phases. For three phase auto-reclosing, for the first shot
only, auto-reclose can be performed without checking that the voltages are in synchronism
by means of a setting. This setting,
CBxL SC Shot 1
, can be set to
Enabled
to perform
synch-checks on shot 1 for CB1 or CB2, or
Disabled
to not perform the checks.
When the circuit breaker has closed, the
Set CB1 Close
(DDB 1565) signal from the
CB autoclose logic
goes high and the reclaim time (“Reclaim Time”) starts. If the circuit
breaker has remained closed and not tripped again when the reclaim timer expires, the
auto-reclose cycle is complete, and signal
CB1 Succ 1P AR
(DDB1571) or
CB1 Succ 3P
AR
(DDB 852) is generated to indicate the successful reclosure. These signals also
increment the relevant circuit breaker successful auto-reclose shot counters
CB1 SUCC SPAR
,
CB1 SUCC 3PAR Shot1
,
CB1 SUCC 3PAR Shot2
,
CB1 SUCC 3PAR
Shot3
and
CB1 SUCC 3PAR Shot4
, as well as resetting the circuit breaker auto-reclose in
progress
CB1 ARIP
signal.
Summary of Contents for MiCOM P54 Series
Page 2: ......
Page 4: ......
Page 5: ...Safety Section P54x EN SS H11 SS SAFETY SECTION...
Page 6: ...P54x EN SS H11 Safety Section SS...
Page 8: ...P54x EN SS H11 Safety Section SS 2 SS...
Page 16: ...P54x EN IT La4 Introduction MiCOM P543 P544 P545 P546 IT...
Page 18: ...P54x EN IT La4 Introduction IT 1 2 MiCOM P543 P544 P545 P546 IT...
Page 28: ...P54x EN IT La4 Introduction IT 1 12 MiCOM P543 P544 P545 P546 IT...
Page 30: ...P54x EN TD La4 Technical Data MiCOM P543 P544 P545 P546 TD...
Page 58: ...P54x EN GS La4 Getting Started MiCOM P543 P544 P545 P546 GS...
Page 78: ...P54x EN ST La4 Settings MiCOM P543 P544 P545 P546 ST...
Page 172: ...P54x EN ST La4 Settings ST 4 94 MiCOM P543 P544 P545 P546 ST...
Page 174: ...P54x EN OP La4 Operation MiCOM P543 P544 P545 P546 OP...
Page 442: ...P54x EN OP B94 Operation OP 5 270 MiCOM P543 P544 P545 P546 OP...
Page 444: ...P54x EN AP La4 Application Notes MiCOM P543 P544 P545 P546 AP...
Page 534: ...P54x EN PL La4 Programmable Logic MiCOM P543 P544 P545 P546 PL...
Page 538: ...P54x EN PL La4 Programmable Logic PL 7 4 MiCOM P543 P544 P545 P546 PL...
Page 602: ...P54x EN PL La4 Programmable Logic PL 7 68 MiCOM P543 P544 P545 P546 Output Contacts PL...
Page 603: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 69 Output Contacts PL...
Page 606: ...P54x EN PL La4 Programmable Logic PL 7 72 MiCOM P543 P544 P545 P546 PL...
Page 616: ...P54x EN PL La4 Programmable Logic PL 7 82 MiCOM P543 P544 P545 P546 Output Contacts PL...
Page 619: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 85 PL...
Page 620: ...P54x EN PL La4 Programmable Logic PL 7 86 MiCOM P543 P544 P545 P546 PL...
Page 621: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 87 PL...
Page 624: ...P54x EN PL La4 Programmable Logic PL 7 90 MiCOM P543 P544 P545 P546 PL...
Page 629: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 95 Output Contacts PL...
Page 630: ...P54x EN PL La4 Programmable Logic PL 7 96 MiCOM P543 P544 P545 P546 PL...
Page 631: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 97 PL...
Page 633: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 99 PL...
Page 637: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 103 PL...
Page 641: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 107 Output Contacts PL...
Page 642: ...P54x EN PL La4 Programmable Logic PL 7 108 MiCOM P543 P544 P545 P546 Output Contacts PL...
Page 643: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 109 LEDs PL...
Page 644: ...P54x EN PL La4 Programmable Logic PL 7 110 MiCOM P543 P544 P545 P546 PL...
Page 645: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 111 PL...
Page 647: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 113 PL...
Page 653: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 119 Output Contacts PL...
Page 655: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 121 Output Contacts PL...
Page 656: ...P54x EN PL La4 Programmable Logic PL 7 122 MiCOM P543 P544 P545 P546 LEDs PL...
Page 663: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 129 PL...
Page 667: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 133 Output Contacts PL...
Page 669: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 135 Output Contacts PL...
Page 671: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 137 PL...
Page 672: ...P54x EN PL La4 Programmable Logic PL 7 138 MiCOM P543 P544 P545 P546 PL...
Page 676: ...P54x EN PL La4 Programmable Logic PL 7 142 MiCOM P543 P544 P545 P546 PL...
Page 681: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 147 Output Contacts PL...
Page 688: ...P54x EN PL La4 Programmable Logic PL 7 154 MiCOM P543 P544 P545 P546 PL...
Page 689: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 155 PL...
Page 690: ...P54x EN PL La4 Programmable Logic PL 7 156 MiCOM P543 P544 P545 P546 PL...
Page 696: ...P54x EN PL La4 Programmable Logic PL 7 162 MiCOM P543 P544 P545 P546 Output Contacts PL...
Page 698: ...P54x EN PL La4 Programmable Logic PL 7 164 MiCOM P543 P544 P545 P546 PL...
Page 701: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 167 PL...
Page 703: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 169 PL...
Page 704: ...P54x EN PL La4 Programmable Logic PL 7 170 MiCOM P543 P544 P545 P546 PL...
Page 705: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 171 PL...
Page 706: ...P54x EN PL La4 Programmable Logic PL 7 172 MiCOM P543 P544 P545 P546 LEDs PL...
Page 708: ...P54x EN MR La4 Measurements and Recording MiCOM P543 P544 P545 P546 MR...
Page 710: ...P54x EN MR La4 Measurements and Recording MR 8 2 MiCOM P543 P544 P545 P546 MR...
Page 726: ...P54x EN FD La4 Firmware Design MiCOM P543 P544 P545 P546 FD...
Page 748: ...P54x EN CM La4 Commissioning MiCOM P543 P544 P545 P546 CM...
Page 754: ...P54x EN CM La4 Commissioning CM 10 6 MiCOM P543 P544 P545 P546 CM...
Page 874: ...P54x EN MT La4 Maintenance MiCOM P543 P544 P545 P546 MT MT...
Page 876: ...P54x EN MT La4 Maintenance MT 11 2 MiCOM P543 P544 P545 P546 MT...
Page 882: ...P54x EN TS La4 Troubleshooting MiCOM P543 P544 P545 P546 TS...
Page 884: ...P54x EN TS La4 Troubleshooting TS 12 2 MiCOM P543 P544 P545 P546 TS...
Page 894: ...P54x EN SC La4 SCADA Communications MiCOM P543 P544 P545 P546 SC...
Page 928: ...P54x EN SG La4 Symbols and Glossary MiCOM P543 P544 P545 P546 SG...
Page 938: ...P54x EN SG La4 Symbols and Glossary SG 14 10 MiCOM P543 P544 P545 P546 SG...
Page 940: ...P54x EN IN La4 Installation MiCOM P543 P544 P545 P546 IN...
Page 974: ...P54x EN IN La4 Installation IN 15 34 MiCOM P543 P544 P545 P546 IN...
Page 976: ...P54x EN VH La4 Firmware and Service Manual Version History MiCOM P543 P544 P545 P546 VH...
Page 1023: ......