User Manual
M3x5/EN M/B
iSTAT M3x5
Page 51
PLEASE NOTE
Customized screens defined here are selected in menu
(KD)
Main menu
Measurements
Present values
Custom
Setting can be made only for 3 customized screens. 4
th
customized screen shows 5
parameters, three from Customized screen 1 and the first two from Customized screen 2.
See example above.
Setting:
(KD)
Main menu
Settings
LCD
Custom screen 1 / 2 / 3 / (4)
Customized screen 1
Customized screen 2
Customized screen 3
(KD)
Main menu
Measurements
Present values
Custom
10.8 Security
Parameter settings are divided into 2 groups regarding security level:
1.
If the passwords are set to ‘AAAA’ (default) there is no restriction to the access of
parameter settings.
2.
Password level 0 (PL0), no password is required and the settings for LCD backlight,
contrast and display language can be modified.
3.
Password level 1 (PL1), the settings for the real time clock and the reset of the energy
registers and MD can be accessed.
4.
Password level 2 (PL2), access is given to all parameter settings.
5.
Change to the language setting is possible without inputting a password. When
language is changed to or from Russian, character transformation has to be taken in
to account, see section 10.4.5.
6.
A Backup password (BP) is used if the passwords at level 1 (PL1) and level2 (PL2)
have been forgotten, and it is different for each device depending on the serial number
of the instrument. The BP password is available from the customer support
department of Alstom Grid, and is entered instead of password PL1 and/or PL2. The
serial number must be supplied when requesting the BP and is defined on the product
label, is available via the display or can be read with
QDSP2
.
Summary of Contents for iSTAT M355