User Manual
M3x5/EN M/B
iSTAT M3x5
Page 111
MODULES
Alarm module
Type Relay
output
Purpose
Alarm output, General purpose digital
output
No. of outputs
2 (Modules 1, 2) or 8 (Modules A, B)
Rated Voltage
230 V
AC/DC
± 20% max.
Max switching current
1000 mA (Module 1, 2)
100 mA (Module A, B)
Contact resistance
≤
100 m
Ω
(100 mA, 24V)
Pulse (Module 1, 2 only)
Max 4000 imp/hour, Min length 100ms
Status (Watchdog) module
Type Relay
output
Number or outputs
1 x wa 1 x relay output
Normal operation
Relays is ON position
Failure detection delay
≈
1.5 s
Rated Voltage
230 V
AC/DC
± 20% max.
Max switching current
1000 mA
Contact resistance
≤
100 m
Ω
(100 mA, 24V)
Energy Pulse module
Type
Optocoupler open collector
Purpose
2 x Pulse output
Maximum voltage
40 V
AC/DC
Maximum Current
30 mA (R
ONmax
= 8
Ω
)
Contact resistance
Programmable (2….999 ms)
Analogue Output module
Output range
0 … 20mA
Accuracy
0.5% of range
Maximum burden
150
Ω
Linearization Linear,
Quadratic
No, of breakpoints
5
Output value limits
± 120% of nominal output
Response time
(measurement
and analogue output)
Depends on setting of general average
interval
0.1s – 5.0 s
Residual ripple
< 1% peak to peak
Tariff Input Module
No of inputs
2
Voltage
5….48 V AC/DC *
110V ± 20% AC/DC *
230V ± 20% AC/DC *
* Depends on built in hardware
Digital Input Module
No of inputs
2 (Modules 1, 2) or 8 (Modules A, B)
Voltage
5….48 V AC/DC *
110V ± 20% AC/DC *
230V ± 20% AC/DC *
* Depends on built in hardware