Table 5:
Suggested Common energy counter resolutions
Current
Voltage
1 A
5 A
50 A
100 A
1000 A
110 V
100 mWh
1 Wh
10 Wh
10 Wh
100 Wh
230 V
1 Wh
1 Wh
10 Wh
100 Wh
1 kWh
1000 V
1 Wh
10 Wh
100 Wh
1 kWh
10 kWh
30 kV
100 Wh
100 Wh
1 kWh
10 kWh
10 kWh *
*
−
Individual counter resolution should be at least 100
Device address
Set MODBUS address for the device. Default address is 33.
Baud rate
Set communication rate. Default rate is 19200 bits/s. This setting is available only when
RS232 / RS485 communication is built in.
Parity
Set communication parity. Default value is “None”. This setting is available only when RS232
/ RS485 communication is built in.
Stop bit
Set communication stop bits. Default value is 2. This setting is available only when RS232 /
RS485 communication is built in.
IP Address
Set correct IP address of the device. Default setting is 0.0.0.0 and represents DHCP
addressing. This setting is available only when Ethernet communication is built in.
TCP Port
Set TCP communication Port. Default value is 10001. This setting is available only when
Ethernet communication is built in.
Subnet mask
Set network subnet mask. Default value is 255.255.255.0. This setting is available only when
Ethernet communication is built in.