Chapter 4 Parameter Index
29
Function
code
Parameter
Setting range
Factory
setting
Modify
flag
Modbus
address
P1.08
S curve start time
10.0~50.0 % (acceleration
and deceleration time )
P1.08+P1.09
≤
90%
20.0%
○
0208
P1.09
S curve
ascending stage
time
10.0~80.0 % (acceleration
and deceleration time)
P1.08+P1.09
≤
90%
60.0%
○
0209
P1.10 Stop
mode
0: Deceleration stop
1: Free stop
2: Decele DC braking
0 ×
020A
P1.11
Stopping DC
braking
frequency
0.00~MIN(50.00Hz, upper
limit frequency )
0.10Hz
○
020B
P1.12 Reserve
-
-
-
P1.13 Reserve
-
-
-
P1.14
Digital setting of
Stopping DC
braking current
0.0~100.0% motor rated
current
0.0%
○
020E
P1.15
Stopping DC
braking time
0.0~30.0s 0.0s
○
020F
P1.16 Reserve
-
-
-
P1.17 Reserve
-
-
-
P1.18 Braking
selection
0: Do not use brake
1: Use energy consumption
braking
1 ×
0212
P1.19
Energy
consumption
braking usage
30.0%~100.0%
Note: It is active for 3015GB
and below built-in models of
this series; automatically add
dynamic braking in
deceleration
100.0%
× 0213
P2: Auxiliary Run
Function
code
Parameter
Setting range
Factory
setting
Modify
flag
Modbus
address
P2.00 Jog
frequency 0.10Hz~upper limit frequency
5.00Hz
○
0300
P2.01
Jog acceleration
time
1.0~3600s 20.0s
○
0301
P2.02
Jog deceleration
time
1.0~3600s 20.0s
○
0302
P2.03 Reserve
-
-
-
P2.04 Reserve
-
-
-
P2.05
Frequency
deviation setting
0.00~2.50Hz 0.10Hz
○
0305
P2.06 Reserve
-
-
-