10
APL48-50LFP liFePO
4
Battery Operation Manual
4.3
– Charge/Discharge Modes and Conditions
Table 4.3 Charge Modes and Conditions
Cell Temperature
Standard Charge
Fast Continuous Charge
Boost Charge(5s)
<
0
℃
No Charge Allowed
No Charge Allowed
No Charge Allowed
0
℃
5
℃
Charge Current: 0.1C
No Charge Allowed
No Charge Allowed
5
℃
10
℃
Charge Current: 0.1C
Charge Current: 0.2C
No Charge Allowed
10
℃
25
℃
Charge Current: 0.2C
Charge Current: 1.0C
No Charge Allowed
25
℃
50
℃
Charge Current: 0.5C
Charge Current: 0.75C
1C Charge is allowed when voltage is
lower than 3.65V
50
℃
60
℃
Charge Current: 0.1C
>
60
℃
No Charge Allowed
Table 4.4 Discharge Modes and Conditions
Cell Temperature
Standard Discharge
Rate Continuous Discharge
Boost Discharge(5s)
<
-40
℃
No Discharge Allowed
No Discharge Allowed
No Discharge Allowed
-40
℃
-20
℃
Discharge Current: 0.1C
No Charge Allowed
No Charge Allowed
-20
℃
0
℃
Discharge Current: 0.1C
Discharge Current: 0.5C
Discharge Current: 1C
0
℃
60
℃
Discharge Current: 0.2C
Discharge Current: 1.0C
Discharge Current: 1C
>
60
℃
No Charge Allowed