APL48-50LFP liFePO

Battery Operation Manual 

  

 

 

When the temperature of the NTC drops to the set value of recovery over-temperature, the BMS 
recovers from over-temperature state, and the red ALM light extinguishes. 

 

APL48150LFP  is  equipped  with  heater,  sampling  temperature  is  0

~  +10

℃ 

when  charging, 

sampling temperature is below 0

℃ 

when standing, heater power supply is 100W, heater starts. 

Heater is optional for other models. 

 

Battery capacity calculation function

 

Cell  algorithm:  About  the  use  of  soc  and  soh,  soc  uses  the  basic  elements  of  the  Ampere 
integration and OCV method. The Ampere integration method and voltage, by the adjustment of 
the  algorithm,  with  higher  precision  data  and  Independent  clock  system,  ensures  reasonable 
display during a single cycle. And the SOC estimation accuracy is 

≤ ± 

2%. 

 

 

Balancing Function

 

When  the  battery  pack  is  charged,  if  the  cell voltage reaches the  equalization  turn-on  voltage, 
and the maximum voltage difference is greater than the equalization voltage difference, the cell 
that  meets  the  condition turns  on  the  equalization function.  Battery  supports  up  to  7  channels 
simultaneously to turn on equalization. The maximum equalization current is about 75mA. 

 

Balance will stop when charging stops or the voltage difference of the cell is less than the setting 
value. 

 

 

Sleep and Wake Function

 

No. 

Sleep condition 

Wake-up condition 

Remark 

 

In the idle state (no charge, discharge, no 
communication), the lowest voltage of any cell is 

lower than the set sleep voltage (can be set), after 
30 minutes, enter normal sleep. 

Charge and discharge, 
communication, reset 

button, soft switch 

The battery with 
a soft switch can 

be waked up 

When the minimum cell voltage is lower than the 

cell over-discharge protection value (can be set) or 
the total voltage is lower than the overall over-
discharge protection value (can be set), and after 1 
minute, the under-voltage sleep is entered. 

Charge, reset button, 

soft switch 

The battery with 

a soft switch can 
be waked up. 

Battery will enter to normal sleep after keeping 

idle state (no charge and discharge, no 
communication) for 24 hours. 

Charge and discharge, 

communication, reset 
button, soft switch 

The battery with 

a soft switch can 
be waked up 

Forcing sleep through the host computer or soft 

switch. 

Reset button, soft switch 

N.A. 

 

 
 

 

 

Summary of Contents for APL 48-50 LFP

Page 1: ...Moorebank NSW 2170 Australia Alpha Power Systems T 02 9602 8331 F 02 9602 9180 E admin alphapower com au W www alphapower com au APL 48 50 LFP Lithium ion Battery Operation Manual APL 48 50 LFP Lithi...

Page 2: ...Charge Performance 8 3 3 Constant Current Discharge Table 8 3 4 Constant Power Discharge Table 8 Part 4 Operation Maintenance 9 4 1 Requirements for Operation Environment 9 4 2 Parameter Settings of P...

Page 3: ...ndles Do not place tools or metal objects on the battery Do not direct access to the battery system to the mains grid power outlet Do not put the battery system into fire do not use or storage the bat...

Page 4: ...ithium iron phosphate battery units in series with the dedicated high performance and high reliability battery management system BMS The output terminal of the battery is connected to the terminal of...

Page 5: ...elay time of the discharge detection the protective plate judges that the over discharge state occurs The green RUN lamp and red ALM lamp are both extinguished discharge MOSFET is closed and the batte...

Page 6: ...he equalization function Battery supports up to 7 channels simultaneously to turn on equalization The maximum equalization current is about 75mA Balance will stop when charging stops or the voltage di...

Page 7: ...able to conduct charging and discharging Note 1 Please refer to Specification of each models for detail BMS parameter setting value 2 LCD display screen is provided as option 3 Anti theft function is...

Page 8: ...of Cells 15 cells Limited Charge Voltage 54 0 V Discharge Cut off Voltage 42 V Standard Charge Current 10 A Standard Discharge Current 10 A Max Continuous Charge Current 50 A Max Continuous Discharge...

Page 9: ...liFePO4 Battery Operation Manual Part 3 Technical Characteristics 3 1 Discharge Performance Fig 3 1 Constant Current Discharge Curve of APL LFP 25 Fig 3 1 Discharge Curve of different temperature of...

Page 10: ...3 33 2 49 1 98 1 65 1 23 0 98 42 0 10 08 4 96 3 97 3 31 2 47 1 96 1 64 1 21 0 96 43 5 10 00 4 92 3 94 3 27 2 45 1 94 1 62 1 19 0 95 45 0 9 91 4 85 3 88 3 22 2 40 1 90 1 58 1 17 0 92 3 4 Constant Power...

Page 11: ...cid batteries can be replaced by lithium battery of APL48 50LFP if power is matched Table 4 2 Parameter settings of power plant for lithium ion battery No Parameters Units Defaults 1 Charge voltage V...

Page 12: ...Charge Current 1 0C No Charge Allowed 25 50 Charge Current 0 5C Charge Current 0 75C 1C Charge is allowed when voltage is lower than 3 65V 50 60 Charge Current 0 1C 60 No Charge Allowed Table 4 4 Dis...

Page 13: ...n port It is adopting RS 232 series port to upload data Contents of data transmit include BMS parameters battery running status alarms etc Generally speed rate of RS 232 is 1200bps RS232 up link commu...

Page 14: ...ation Batteries shall not be placed in direct sunshine or close to heat source Batteries shall be installed in place with good ventilation to assure enough heat dissipation Batteries shall be placed i...

Page 15: ...etween battery module and power plant shall be less than 2 0m To make sure similar voltage drop of cable for each battery length of all positive and negative cables should be the same Color for cable...

Page 16: ...on cable between battery module and power plant shall be less than 0 5V 4 7 Storage The battery storage shall be in the clean and dry ventilation room at the temperature of 0 40 C and shall keep out o...

Page 17: ...ged Normal charge management Do not need to solve Protection against over voltage Do not need to solve Protection against over temperature or under temperature Ambient temperature is lowerthan 10 or h...

Page 18: ...lash 1 Flash 2 Alarm light goes off after a few seconds Over temperature under temperature over current protection Flash 1 Flash 2 Discharge Normal Normally on OFF According to the SOC Alarm Normally...

Page 19: ...ave PACK ON OFF OFF ON OFF OFF PACK 10 001001 Slave PACK OFF ON OFF ON OFF OFF PACK 11 001010 Slave PACK ON ON OFF ON OFF OFF PACK 12 001011 Slave PACK OFF OFF ON ON OFF OFF PACK 13 001100 Slave PACK...

Page 20: ...CK OFF OFF OFF OFF ON ON PACK 49 110000 Slave PACK ON OFF OFF OFF ON ON PACK 50 110001 Slave PACK OFF ON OFF OFF ON ON PACK 51 110010 Slave PACK ON ON OFF OFF ON ON PACK 52 110011 Slave PACK OFF ON OF...

Page 21: ...system uses through 6Pin straight PCB welding socket RJ11 to provide RS 232 protocol the pin assignment of RJ11 is defined as follows Table 1 RJ11 Pin Assignment 2 RS 485 The system uses through 8Pin...

Reviews: