CAUTION!
Terminal block covers and the battery harness restraining bracket MUST be used and are available from
Alpha and Outback Energy (part number 740-698-21). If the Alpha FXM end application is mounted inside an
enclosure or in an area restricted to authorized personnel, then the covers and bracket may or may not be
needed.
To meet NEBS Level 1 specifications when you are installing this unit in a rack or frame, do the following:
1. Before installation, clean all attachment points on the Alpha FXM, rack and mounting brackets and bring
them to a bright finish. Then coat them with an anti-oxidant such as Sanchem Inc. No-Ox ID “A-Special
Electrical Grade” or equivalent.
2. Attach the mounting brackets with the thread forming screws and the paint piercing washers provided with
the brackets to insure adequate grounding between the Alpha FXM chassis and the rack.
Figure 7 — Mounting the Alpha FXM Mounting brackets position for rack mounting. Rotate to fit either 19" or 23"
racks.
For the FXM 1100/2000 units only, the control panel and the power connection panel can be rotated to suit your
needs. To rotate either one, unscrew the screws in each corner, remove the panel, rotate it and reinstall the screws.
CAUTION!
Use care to avoid damaging or pulling out the wires or the ribbon cables when rotating the panels.