In the
Battery Configuration
table,
Temperature Compensation
(default 0.0mV/Cell/°C for bulk charger) and
Max Charger Current
have the same function as the Standard charging method.
The following three parameters are only available when the Bulk battery charging method is selected:
Parameter
48V
24V
Default Minimum Maximum Default
Minimum Maximum
Max Charger Voltage (Vdc)
53.5
52
56
26.8
26
28
Float Charger Voltage (Vdc)
53.5
52
56
26.8
26
28
Low Voltage Warning*(Vdc)
44
44
47
22
22
23
*Low voltage warning value has to be higher than
Low Voltage Disconnect
and lower than
Low Voltage
Reconnect
Low Voltage Disconnect
and
Low Voltage Reconnect
have the same function as the Standard charging
method.
UPS Maintenance > Inverter
Figure 24 — UPS Maintenance: Inverter screen
Inverter Enabled/Disabled
Enabled: the inverter can function depending on the setting of the Inverter On/Off field. Disabled: the FXM will not
go into Inverter mode when it loses AC power.
Inverter On/Off
Selecting inverter On/Off will not turn on the inverter unless inverter is enabled first.
Inverter Off Delay Time
Used to set a delay before the inverter switches off to allow time for switching off critical loads. The set Inverter
ON/OFF delay is only available when the Alpha FXM is in the Battery or Standby modes.
The delay can be adjusted in 1 second steps with a default setting of 0 seconds to a maximum of 600 seconds
(10 minutes). The delay is only available in the Standby or Inverter modes. Once the Alpha FXM returns to the
Line mode, the delay resets to 0 seconds.
Page
41
to
95