25
Subject to technical amendments without notice | 83050700gUK – Translation of the original operating manual | ait-deutschland GmbH
Unit designation
Heat pump type
Brine/water ı Air/water ı Water/water
• applicable ı — not applicable
Installation location
Indoors ı Outdoors
• applicable ı — not applicable
Conformity
CE
Performance data
Heating capacity/COP at
W10/W35
Standard point to EN14511
2 compressors
1 compressor
kW ı …
kW ı …
W10/W45
Standard point to EN14511
kW ı …
W10/W35
Standard point acc. to EN255
2 compressors
1 compressor
kW ı …
kW ı …
Limits of use
Heating circuit
°C
Heat source
°C
additional operating points
…
Sound
Sound pressure level averaged at distance of 1m around the machine (in free field)
dB(A)
Sound power level to EN12102
dB
Heat source
Flow rate: minimum flow ı nominal flow ı maximum flow
l/h
Pressure loss heat pump ∆p (with cooling ∆pK) ı Flow rate
bar (bar) ı l/h
Free compression heat pump ∆p (with cooling ∆pK) ı Flow rate
bar (bar) ı l/h
Recommended heat source pump
Power consumption of the heat source pump at nominal throughput
kW
Nominal power / electricity consumption of heat source pump
kW ı A
Total compression of the recommended heat source pump at nominal throughput
bar
Dirt trap, to be installed upstream of the heat pump (included in additional box)
Heating circuit
Flow rate: minimum flow ı nominal flow ı maximum flow
l/h
Pressure loss heat pump ∆p (with cooling ∆pK) ı Flow rate
bar (bar) ı l/h
Free compression heat pump ∆p (with cooling ∆pK) ı Flow rate
bar (bar) ı l/h
General unit data
Dimensions (see dimensioned drawing for the specified unit size)
unit size
Total weight (including cooling)
kg (kg)
Additional weight module 1
kg
Additional weight module 2
kg
Connections
Heating circuit
…
Heat source
…
Refrigerant
Refrigerant type ı Quantity
… ı kg
Electrics
Voltage code ı all-pole circuit breaker heat pump *)
… ı A
Voltage code ı circuit breaker control voltage *)
… ı A
Voltage code ı circuit breaker electric heating element *)
ı A
Heat pump
Effective power consumption in the standard point W10/W35 to EN14511: Power consumption ı current consumption ı cosφ
kW ı A ı …
Maximum machine current within the use limits
A
Starting current: direct ı with soft starter
A ı A
Degree of protection
IP
Output, electric heating element 3 ı 2 ı 1 phase
kW ı kW ı kW
Components
Circulation pump, heating circuit at nominal flow rate: Power consumption ı current consumption
kW ı A
Circulation pump, heat source at nominal flow rate: Power consumption ı current consumption
kW ı A
Passive cooling function
Specification only for units with designator K: Cooling output at nominal flow rate (15°C heat source, 25°C heating water)
kW
Safety equipment
Safety component heating circuit ı Safety component heat source
Incl. in scope of delivery: • yes — no
Heating and heat pump controller
Incl. in scope of delivery: • yes — no
Electronic soft starter
integrated: • yes — no
Expansion vessels
Heat source: Scope of delivery ı Volume ı Initial pressure
• yes — no ı l ı bar
Heating circuit: Scope of delivery ı Volume ı Initial pressure
• yes — no ı l ı bar
Overflow valve
integrated: • yes — no
Vibration decouplers
Heating circuit ı heat source
Incl. in scope of delivery: • yes — no
UK813241-a
*) comply with local regulations n.d. = not detectable
WWC 100H/X
— ı — ı •
• ı —
•
—
11,0 ı 5,6
—
—
11,2 ı 5,7
20 - 65
7 - 25
—
40
53
2200 ı 2200 ı 4100
0,06 ( —) ı 2200
—
Grundfos SP 3A-6
0,33
0,38 ı 1,4
3,00
5/4“
950 ı 1900 ı 2400
—
0,34 ( —) ı 1350
1
213 (—)
—
—
R 5/4“ AG
R 5/4“ AG
R407c ı 2,95
3~/PE/400V/50Hz ı C10
1~/N/PE/230V/50Hz ı B10
3~/N/PE/400V/50Hz ı C10
1,96 ı 3,8 ı 0,74
5,9
30 ı —
20
6 ı 4 ı 2
0,07 ı n.n.
— ı —
—
• ı —
•
—
— ı — ı —
• ı 25l ı 1,5
•
• ı •
813233-e
WWC 220H/X
— ı — ı •
• ı —
•
—
21,8 ı 5,7
—
—
21,8 ı 6,1
20 - 65
7 - 25
—
43
56
4400 ı 4400 ı 7700
0,23 ( —) ı 4400
—
Grundfos SP 5A-6
0,54
0,55 ı 2,2
2,67
6/4“
1900 ı 3700 ı 4700
—
0,61 ( —) ı 3700
1
235 (—)
—
—
R 5/4“ AG
R 5/4“ AG
R407c ı 4,5
3~/PE/400V/50Hz ı C13
1~/N/PE/230V/50Hz ı B10
3~/N/PE/400V/50Hz ı C16
3,82 ı 7,0 ı 0,79
11,0
— ı 30
20
9 ı 6 ı 3
0,18 ı n.n.
— ı —
—
• ı —
•
•
— ı — ı —
• ı 50l ı 1,5
•
• ı •
813237-g
WWC 190H/X
— ı — ı •
• ı —
•
—
18,6 ı 5,6
—
—
18,6 ı 5,7
20 - 65
7 - 25
—
40
53
3800 ı 3800 ı 6500
0,16 ( —) ı 3800
—
Grundfos SP 3A-6
0,38
0,38 ı 1,4
1,76
5/4“
1600 ı 3100 ı 3900
—
0,52 ( — ) ı 2200
1
227 (—)
—
—
R 5/4“ AG
R 5/4“ AG
R407c ı 4,3
3~/PE/400V/50Hz ı C13
1~/N/PE/230V/50Hz ı B10
3~/N/PE/400V/50Hz ı C16
3,27 ı 6,0 ı 0,79
9,4
— ı 28
20
9 ı 6 ı 3
0,17 ı n.n.
— ı —
—
• ı —
•
•
— ı — ı —
• ı 35l ı 1,5
•
• ı •
813236-e
WWC 160H/X
— ı — ı •
• ı —
•
—
14,7 ı 5,6
—
—
14,8 ı 5,7
20 - 65
7 - 25
—
40
53
3000 ı 3000 ı 5200
0,11 ( —) ı 3000
—
Grundfos SP 3A-6
0,38
0,38 ı 1,4
2,57
5/4“
1300 ı 2500 ı 3100
—
0,40 ( — ) ı 1800
1
219 (—)
—
—
R 5/4“ AG
R 5/4“ AG
R407c ı 3,95
3~/PE/400V/50Hz ı C10
1~/N/PE/230V/50Hz ı B10
3~/N/PE/400V/50Hz ı C16
2,6 ı 4,6 ı 0,81
7,5
— ı 25
20
9 ı 6 ı 3
0,16 ı n.n.
— ı —
—
• ı —
•
•
— ı — ı —
• ı 35l ı 1,5
•
• ı •
813235-e
WWC 130H/X
— ı — ı •
• ı —
•
—
12,9 ı 5,5
—
—
12,7 ı 5,7
20 - 65
7 - 25
—
40
53
2600 ı 2600 ı 4500
0,1 ( —) ı 2600
—
Grundfos SP 3A-6
0,38
0,38 ı 1,4
2,85
5/4“
1100 ı 2200 ı 2800
—
0,46 ( —) ı 1600
1
216 (—)
—
—
R 5/4“ AG
R 5/4“ AG
R407c ı 3,5
3~/PE/400V/50Hz ı C10
1~/N/PE/230V/50Hz ı B10
3~/N/PE/400V/50Hz ı C10
2,35 ı 4,4 ı 0,77
6,9
— ı 20
20
6 ı 4 ı 2
0,16 ı n.n.
— ı —
—
• ı —
•
•
— ı — ı —
• ı 25l ı 1,5
•
• ı •
813234-f