Subject to change without notice | 83057200dUK – Translation of the original operating manual | ait-deutschland GmbH
9. Ensure that the U-clip has latched into position
correctly:
9
Valve motor sits securely on the 3-way changeo-
ver valve.
9
Both prongs of the U-clip sit on the lug.
9
The tips of the U-clip are visible by approx. 2 mm
QRWVLJQL¿FDQWO\PRUH
10. Screw the front panel of the module box.
8 Insulate hydraulic connections
1. Insulate heating circuit and heat source according
to the local regulations.
2.
2SHQVKXWRႇGHYLFHV
3.
3HUIRUPDSUHVVXUHWHVWDQGFKHFNIRUOHDNV
4. Insulate the internal piping of the module box with
WKH LQVXODWLRQ PDWHULDO IURP WKH VHSDUDWH SDFN
included.
5. Insulate external piping on site.
6.
,QVXODWHDOOFRQQHFWLRQV¿WWLQJVDQGSLSHV
7.
,QVXODWHKHDWVRXUFHVRWKDWLWLVYDSRXUGLႇXVLRQ
tight.
8. Insulate the heating circuit of units with cooling
YDSRXUGLႇXVLRQWLJKWWRR
9
6HWWKHRYHUÀRZYDOYH
NOTE
Ɣ
The activities in this section are only nec-
HVVDU\IRULQOLQHWDQNLQWHJUDWLRQ
Ɣ &RPSOHWHWKHZRUNVWHSVTXLFNO\RWKHUZLVH
the maximum return temperature can be
exceeded and the heat pump switches to
high-pressure fault.
Ɣ 7XUQ WKH DGMXVWLQJ NQRE DW WKH RYHUÀRZ
valve to the right to increase the tempera-
WXUHGLႇHUHQFHWKHWHPSHUDWXUHGURSWXUQ
it to the left to reduce it.
9
6\VWHPLVUXQQLQJLQKHDWLQJPRGHLGHDOO\LQFROG
condition
1. In case of low heating curve: Set the system to
³)RUFHG KHDWLQJ´
Æ
operating manual of the
KHDWLQJDQGKHDWSXPSFRQWUROOHU
2.
6KXWRႇYDOYHVWRWKHKHDWLQJFLUFXLW
3.
(QVXUH WKDW WKH WRWDO ÀRZ LV URXWHG YLD WKH RYHU
-
ÀRZYDOYH
4.
5HDG RXW WKH ÀRZ DQG UHWXUQ WHPSHUDWXUH DW WKH
KHDWLQJ DQG KHDW SXPS FRQWUROOHU
Æ
operating
PDQXDORIWKHKHDWLQJDQGKHDWSXPSFRQWUROOHU
5.
7XUQWKHDGMXVWLQJNQRERIWKHRYHUÀRZYDOYH
XQWLO WKH WHPSHUDWXUH GURS EHWZHHQ WKH ÀRZ
and return temperature is set as follows:
Ɣ
at heat source temperature 0 °C: 8 K
Ɣ
at heat source temperature 10 °C: 10 K
6. Open valves to heating circuit.
7. Reset the heating and heat pump controller.