12
Subject to change without notice | 83059000dUK – Translation of the original operating manual | ait-deutschland GmbH
2. Secure the heat pump module to the handcart
with lashing straps.
3. Transport the heat pump module to the installation
site.
5.4 Installation
Installation area and space requirements
NOTE
Note and follow the local regulations and
standards regarding the installation area and
space requirements. The table shows the
regulations to EN 378-1 relevant in Germany.
Refrigerant
Limit value [kg/m³]
R 134a
0.25
R 404A
0.52
R 407C
0.31
R 410A
0.44
(
“Technical data/Scope of supply” on page 23).
Minimum room volume =
Refrigerant capacity [kg]
Limit value [kg/m³]
NOTE
If several heat pumps of the same type are
installed only one heat pump need to be
taken into account. If several heat pumps
of different types are installed, only the heat
pump with the largest refrigerant volume
needs to be taken into account.
Minimum volume corresponds to the requirements
for the refrigerant used.
Installation inside the building only.
Installation area is dry and frost-free.
Clearance dimensions are met (
“Installation
plans” on page 31).
The surface/floor is suitable for installation of the
unit:
●
Level and horizontal
●
Load-bearing capacity for the unit's weight
NOTE
The sound emissions of the heat pumps must
be taken into account in the respective instal-
lation plans for air/water heat pumps. The re-
spective regional regulations must be com-
plied with.