background image

 Page 4

900-0125-12-01 Rev A

 

©2017 OutBack Power Technologies.  All Rights Reserved.

 Page 5

Main Menu

All programming is accessed from the 

Main Menu

, which includes the following:

o

Settings

 

(System, Inverter, Charge Controller, Battery Monitor, MATE3s) (see below)

o

Profile Wizard 

(

W

) (see page 40)

o

Device Data Logs 

(

D

) (see page 45)

o

Event Logs 

(

E

) (see page 47)

o

Firmware Updates 

(see page 48 and the 

MATE3s Overview Guide

)

Each menu has a set of menu options.  Each menu option has a set of menu items.

System 
Settings (S)

The 

Main Menu

 selection 

for this screen is 

Settings

but the actual screen name 
is 

System Configuration

.  

S-1

.

System Information

S-2

.

Save/Restore
Configuration 

S-3

.

OPTICSre

S-4

.

Firmware Versions

S-5

.

Serial Numbers

S-6

.

Date and Time

S-7

.

LCD Display

S-8

.

Sound

S-1. System

Information

This screen contains a 
basic outline of the 
system.  Many of these 
settings inform other 
system functions.



Type* 

either 

Off Grid

,

Grid Tied

, or 

Backup



Array Wattage* 

Allows for a PV array(s) 
with total wattage rating of 

0

 to 

50

 kW



Generator kW Rating* 

Allows for a generator with 
a rating of 

0

 to 

250 

kW



Max Inverter kW* 

Allows for an inverter
system with total wattage
rating of 

0

 to 

72 

kW

NOTE

:  The letter codes for each 

branch of the 

Settings 

menu are 

continued on subsequent pages 
under the appropriate sections.  

IMPORTANT:

  

If multiple inverters are used in the installation, make certain to change settings 
as appropriate for each inverter on its assigned port.  Changing settings for a 
single inverter in a multiple-inverter system may result in conflicts in operation.    



Charge controller 

Settings

 

(

C

)

 

are described beginning on page 18.  For details about a

FLEXmax or FLEXmax Extreme charge controller, see the controller literature.  The 

MATE3s can monitor, but not program, an MX60 controller.



Battery monitor 

Settings 

(

B

) for the FLEXnet DC are described beginning on page 22.

For details about the FLEXnet DC, see the product literature. 



MATE3s function 

Settings

 (

M

) are for device functions with control logic based in the

MATE3s (AGS, HBX, etc.)  These are described beginning on page 24.

NOTE

:  Once the settings have been changed to match the configuration, they are 

stored in the static memory of the MATE3s.  Once the configuration is established, 
save the data to an SD card.  That way the configuration can be restored without 
having to repeat each setting individually.  (See 

S-2

.)

Settings Menus

This menu accesses additional menus with 

settings for the system and for individual devices.



System 

Settings

 (

S

)

 

apply to overall system functions (date and time,

communication options, etc.).  See the 

System Settings

 section.



Device 

Settings

 

are used to program the system components (inverter, charge

controller, battery monitor, MATE3s).



Inverter 

Settings

 

(

I

) are described beginning on page 10.  See the inverter literature

for details about inverter functions.

Recommended Programming Order

It is recommended that programming proceed in the following order.

1) Establish Profile Wizard settings (

W-4

).

2) Save the Profile (as applicable in either 

W-1

W-2

, or 

W-3

).

3) Program the Profile (as applicable in either 

W-1

W-2

, or 

W-3

).

4) Program any other custom settings.
5) Save the System Configuration (

S-2

).

6) When restoring settings in the future, restore the System Configuration instead of the

Profile Wizard.  (See the Profile Wizard on page 40 for more information.)

S-9

.

Ethernet Addresses

S-10

.

Ethernet Ports

S-11

.

Data Stream

S-12

.

Battery Voltage
Min/Max Reset

 

S-13

.

Clear Internal
Data Log

 

S-14

.

System Name

S-15

.

Installer Information

S-16

.

Installer Settings

A. To save a configuration to an SD card:

If other configurations have been saved on the SD card, 
a list will be displayed. Choose Option 1 or 2. 

NOTE

:  If the SD card is empty, pressing the 

<

Save

> soft key will automatically default to Option 2.

1.

Select a name on the list with the control wheel.
Press <

Save

> to save the new settings over the

selected configurations.  

Saving to SD Card

 will be

displayed.  Proceed to 3.

OR

2.

Press <

New

> to create a new configuration

name.  (8 characters maximum)



Use the control wheel to scroll through the

available characters.



Use <

> or <

>

 

to move to the desired

character location.



Use <

Delete

> to erase characters when

highlighted.

Press <

Save

> to save the new configuration name.  

Saving to SD Card

 will be displayed. 

In either case: 
3.

Wait for the confirmation screen to appear.
After the screen appears, press <

Continue

>

to return to the 

Main Menu

.



Nominal Voltage 

Allows for a battery bank
with a voltage of 

12

24

,

36

48

, or 

60 

Vdc.



Battery Ah 

Allows for a bank with a
total amp-hour rating of

25

 to 

10,000 

Ah



Generator Type 

Allows for an 

AC 

or 

DC

generator, or 

None



Max Charger kW* 

Allows for a system with a
total charger rating of 

0

 to

60 

kW

S-2. Save/Restore Configuration

A configuration is the sum of all MATE3s settings 

for all devices.  This menu allows for saving a 

configuration to an SD card after programming is complete.  

It can restore a lost or erased configuration from the SD card to the MATE3s.  It can 

also copy a configuration from an SD card to an identical system.  
To save or update, select 

Save Configuration

 and follow the 

A

 steps.  To restore 

from an SD card, select 

Restore Configuration

 and follow the 

B

 steps.

NOTE

:  The Profile Wizard (see section 

on page 40) has similar functions.  However, it 

does not affect the entire system configuration and is not interchangeable with this function. 

See Recommended Programming Order.

B. To restore a configuration from

an SD card:

1.

If other configurations have been saved on
the SD card, a list will be displayed.  Use the
control wheel to select the name of the
configuration that is to be restored.

2.

Press <

Restore

> to start the process.  Wait

for the confirmation screen to appear.

3.

After the screen appears, press <

Continue

>

to return to the 

Main Menu

.

For example, charge controller 
setting menu items are labeled 

C-1

C-2

C-3

, and so on.

1

2

3

1

2

3

System Information

Main Menu

Summary of Contents for Out Back Power MATE3s

Page 1: ...CK POWER TECHNOLOGIES a MAKES NO WARRANTY AS TO THE ACCURACY SUFFICIENCY OR SUITABILITY OF ANY TECHNICAL OR OTHER INFORMATION PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION b ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSS OR DAMAGE WHETHER DIRECT INDIRECT CONSEQUENTIAL OR INCIDENTAL WHICH MIGHT ARISE OUT OF THE USE OF SUCH INFORMATION THE USE OF ANY SUCH INFORMATION WILL BE ENTIRELY AT THE USER S...

Page 2: ...stop a generator The MATE3 allows a user to view monitor and establish all the settings and values that occur while the system is running Occasionally components may be added or upgraded electrical loads increase or patterns of usage may change These settings and values can be adjusted to match On screens with set points the control wheel E serves two functions navigation and set point adjustment ...

Page 3: ...ommended Programming Order It is recommended that programming proceed in the following order 1 Establish Profile Wizard settings W 4 2 Save the Profile as applicable in either W 1 W 2 or W 3 3 Program the Profile as applicable in either W 1 W 2 or W 3 4 Program any other custom settings 5 Save the System Configuration S 2 6 When restoring settings in the future restore the System Configuration ins...

Page 4: ...s when a button is pushed or the control wheel is used Button Beep Enabled or Disabled Wheel Click Enabled or Disabled IMPORTANT Some features are dependent on time and date settings Be sure to adjust these settings for the proper time and date for the location of the installation The MATE3s clock does not automatically adjust for daylight savings time The MATE3s does automatically adjust for leap...

Page 5: ... maximum This name is displayed on the Home screen Set User Access Level A This menu allows one of four different user access levels UAL to set points for programming Full Access Level 1 UAL1 This allows full access to all available menus This is the same access permitted by the installer password It is the default setting Advanced Access Level 2 UAL2 This allows access to many user menus It also ...

Page 6: ... Gen AC Input Voltage Limits FX class Pulse Spacing Adjusts the time between search pulses in single AC cycles Shorter spacing will detect loads more quickly This consumes more power o I 8 Auxiliary Output Relay o I 9 Inverter Stacking o I 10 Power Save Ranking o I 11 Grid Tie Sell B A C D I 3b Grid and Gen Input Voltage Limits FX class only The inverter will not connect to an AC source unless spe...

Page 7: ...epicted On activates the AUX output immediately It displays Manual On and remains continuously active until Off is selected Auto activates the AUX output according to the Aux Mode automatic criteria When activated it displays Auto On otherwise it displays Auto Off Off deactivates the AUX output It displays Manual Off Note that the AUX output may still activate from the settings of inverter or MATE...

Page 8: ...nverter for the L2 output in a split phase system B Phase C Phase Master The subphase master inverters for the B or C outputs in a three phase system 3p Master or 3phase Master The primary inverter for three phase systems that include the selection 1 2ph Master as shown above The 3p Master is Phase A 3phase Classic B C or 3p OB Slave A B C A secondary inverter for three phase systems Used in model...

Page 9: ... will appear Pressing this key returns the screen to the Inverter menu NOTE Some items are retained at the present setting even when the inverter is reset to factory defaults The retained settings include the Output Voltage all items in the Calibrate menu Model Select and all items in the Grid Interface Protection menu This menu contains sensitive inverter settings Some settings relate to regional...

Page 10: ...ler Owner s Manual features this as an option under RTS Compensation Limited Lower and Upper Battery Voltage Adjust the lowest and highest allowed compensated voltage The Owner s Manual features these as an option under RTS Compensation See page 42 for the effects of the Profile Wizard on both settings C 4 Battery Equalize CAUTION Battery Damage Do not equalize any sealed battery types VRLA AGM Ge...

Page 11: ... reaching Disconnect Disconnect Delay The time after reaching Disconnect before the output is activated Float activates the AUX output when the charge controller enters the Float stage It can operate a charged indicator Not depicted No settable parameters Remote allows the AUX output to be activated by manual or automatic commands based in the MATE3s such as AGS Not depicted No settable parameters...

Page 12: ...tivates the relay by automatic criteria according to the option selected in Relay Set Points Off deactivates the relay and prevents any of the FLEXnet Relay Set Points options from working Note that even if the relay output is set to Off it may still be activated by an external option such as AGS See page 25 Invert Logic Switches the relay s function from N O a normally open state to N C a normall...

Page 13: ...ect to the inverter s GEN terminal input when using AGS If the input priority is set to GRID and the GRID terminals are energized an automatically controlled generator will shut down AGS turns on the inverter s charger even if it had previously been manually disabled AGS Topics These menus show the different topics settings and starting conditions for AGS AGS screens and topics included under M 1 ...

Page 14: ...nge varies with battery voltage NOTE The Quiet Time settings overrides the settings and prevents an automatic start The exception is 2 Minute Start As an emergency set point it will start the generator regardless of Quiet Time settings Enabled either enables Y or disables N the Load Start function Start the load size 0 to 50 kW which requires the generator to start following the Delay time 1 to 24...

Page 15: ...ints Voltage Load Must Run Exercise etc preventing the generator from starting automatically The only exception is 2 Minute Start which is considered an emergency start set point and which will start the generator regardless of Quiet Time settings M 1 AGS continued Set Generator Total Run Time The total running time for an automatic generator is displayed on the Generator Status screen which is ac...

Page 16: ... shows the reason for starting under Last Run The first two columns in the table below are a list of start reasons The remaining columns display the possible reasons for the generator to stop The possible stop reasons are connected to the start reasons For example a generator which started due to Load kW can stop due to reduction of load kilowatts due to Quiet Time or manually However it will not ...

Page 17: ...ogging to the SD card It does not turn off data logging to the internal flash memory Compact records only the minutes and seconds for each interval recorded SD Card DataLog Write Interval the interval 1 to 60 seconds at which data is automatically downloaded to the SD card SD Card Icon Front Back SD Card Clearance The data log shown in this example is arranged by date and time It shows all devices...

Page 18: ...ters However it is not compatible with Mini Grid and cannot be used at the same time To prevent conflicts when using HBX mode make certain not to select Mini Grid Selection of AC input modes can be found on page 11 Information on Mini Grid and other modes can be found in the inverter Operator s Manual HBX is also incompatible with the Grid Use Time and Load Grid Transfer functions in the MATE3s Th...

Page 19: ...e If a start time equals a stop time no action will be taken and the time period is ignored If the battery voltage falls below the inverter s Low Battery Cut Out voltage the inverter will automatically connect to the AC input source regardless of the time of day setting M 5 Load Grid Transfer The MATE3s can force all inverters to automatically reconnect to the utility grid even if the normal mode ...

Page 20: ...active function to be turned off at midnight each night This function allows the charge controllers to complete a charge cycle at the beginning of the next day before the system begins selling It prevents the batteries from remaining at or below the Sell voltage for extended periods without receiving a full charge If grid interactive inverters are not present this item is inoperative Options are N...

Page 21: ... complete press Exit to return to the Main Menu K W 2 Using Existing Profiles If the most recent profile was lost or changed it can be retrieved from an SD card and applied to the system If the profile was not ideal any existing value can be changed before re applying the profile To apply a profile that was previously saved 1 From the Profile Wizard menu select Existing Profile This will take the ...

Page 22: ...System Type B System Type Off Grid Grid Tied Backup System Voltage Vdc B C Array Wattage Battery Type FLA Gel AGM and Capacity Ah Wizard Generator Configuration F Generator Installed Y or N Generator Type AC or DC and Size kW Generator Start Manual or Auto AUX Output Port F G Wizard AC Configuration D AC Output Voltage Vac AC Phase Single Split 3 Phase AC Input Breaker Size Aac Maximum Output Load...

Page 23: ...e new data log name Saving to SD Card will be displayed In either case C Wait for the confirmation screen to appear After the screen appears press Continue to return to Upload and Save Data Log B A C Date AH 0 38 kWh Max Amps 0 38 0 9 36 Max Watts 52 48 32 0 8 1 hour 1 hour FLEXmax Data Log 6 13 15 6 12 15 6 11 15 Absorb Time 0 00 0 00 0 00 Float Time 0 00 0 00 0 00 Min Battery V 24 1 24 1 24 1 Ma...

Page 24: ...ard or deleted from the MATE3s internal memory o To Save an Event Log E 1 o To Read an Event Log File from the SD Card E 2 o To Delete an Event Log E 3 E 1 To Save an Event Log To create a data log for the FLEXmax Charge Controller 1 From the Event Logs menu select Save Events to SD Card 2 On the Date Range set point use the control wheel to select the date for the event log or logs to be saved to...

Page 25: ... OutBack product to which it is connected The OutBack products may not be powered up or connected Symptom Possible Remedy Check all OutBack devices for correct operation Check or replace the CAT5 cable running from the MATE3s to the OutBack product The left hand RJ45 port on the back of the MATE3s is used for computer communications It cannot power a MATE3s Make sure the CAT5 cable is plugged into...

Page 26: ...r Technologies All Rights Reserved 2 Check the LED indicator o A flashing EVENTS indicator means a warning has occurred o A solid EVENTS indicator may mean that the system has shut down due to an error If Advanced Generator Start AGS is in use it may also mean the system has suffered an AGS fault See the MATE3s Overview Guide and the inverter literature for more information on warnings and errors ...

Reviews: