___________________________________________________________________
Alpha ESS Co., Ltd.
Page 17 of 40
Your Smart Energy
Step 12:
Screw off the big and small waterproof terminals and pass the network
cable through the terminals, into the switch box. At the same time connect the
power cable of output side through waterproof terminal following the diagram.
(Here the network cable is not equipped with RJ45 plug).
Figure 21 Network Cable Connection Diagram
Step 13:
Lock waterproof connector, plug in the RJ45 plugs on LAN1 and Me-
ter
’s ends inside cable box, and then plug in RJ45 and cable on the other side
of LAN1 and Meter’s ends outside of cable box (leave some length as the other
side might need to be connect to router or meter). At the same time, connect
RJ45 into BAT end inside of cable box and leave the outside end there for now).
NOTE: the current of the breaker that connects the inverter must be
more than 25A.
Figure 22 Inverter Wiring Completion Diagram
Communication Baffle