Installation
•
places with flammable materials or gases or an explosive atmosphere.
•
places without clearance of right photo shows.
Restricted Locations
The battery system shall
not be
installed —
(a) in restricted locations, as defined for switchboards in AS/NZS 3000;
(b) within 600 mm of any hot source, such as water unit, gas heater, air conditioning unit
or any other appliance.
(c) within 600 mm of any exit;
(d) within 600 mm of any window or ventilation opening;
(e) within 900 mm of access to 240 Vac connections; and
(f) within 600 mm of side of other equipment.
An eSTORE-BAT-10.3 installed in any corridor, hallway, lobby or the like leading to a fire
exit shall ensure sufficient clearance from the ESTORE-BAT-10.3 for safe egress and no
less than 1 m.
An eSTORE-BAT-10.3 is considered a source of ignition and therefore shall not be installed
within hazardous area for gas cylinders containing heavier than air gasses and gas relief
vent terminal as defined in AS/NZS 3000.
Barrier to habitable rooms
To protect against the spread of fire to habitable rooms, where the eSTORE-BAT-10.3 is
mounted on, placed against a surface of a wall or structure that has a habitable room on
the other side, the wall or structure shall be a suitably non-combustible barrier. If the
mounting surface itself is not made of a suitably non-combustible material, a non-
combustible barrier may be placed between the M4856-P and the surface of a wall or
structure.
Where the eSTORE-BAT-10.3 is located on or within 300mm of the wall or structure
separating it from the habitable room, the barrier shall extend —
(i) 600 mm beyond the vertical sides of the ESTORE-BAT-10.3;
(ii) 1200 mm above the ESTORE-BAT-10.3; and
(iii) to the extent of the bottom of the ESTORE-BAT-10.3
Where the top of the ESTORE-BAT-10.3 is within 1200 mm of the ceiling or structure above
the ESTORE-BAT-10.3, the ceiling or structure surface shall be suitably non-combustible
for an area of 600 mm past the extremities of the ESTORE-BAT-10.3.
ESTORE-BAT-10.3 shall be mounted with the highest point no greater than 2.2 m above