11
III/ Electrical connection
1
2
To reveal the lower section, slide cover up about 15cm.
Whilst sliding cover upwards, pull cover gently towards you.
This will ensure it finds the locking slot.
Box as you find it, closed. Unscrew the 4 screws on the
underside of the SolShare to allow access to connection
terminals. Retain screws to replace later.
Important:
The cover should lock into place when it’s pulled up properly. Before beginning wiring ensure cover is locked in
place by pulling down firmly. To bring cover back to initial position, lift cover upwards and away from you, then
allow to slide down back into place.
A. Input / Output Connections
1. Lift up cover to reveal the lower section of the box, where the electrical connections are made.
INPUT
SOLAR
OUTPUT
1, 2
OUTPUT
3 , 4
OUTPUT
5 , 6
OUTPUT
7 , 8
DEMAND
CT INPUT
REDUNDANT
HOLE, LEAVE
PLUG IN
PLACE
OUTPUT
9 , 10
COVER
RETAINER
SCREWS
The AC cables
Please choose appropriately gauged
cables as per solar system size. The
use of four core and earth (4c+e) is
recommended. All input and output
cables should be rated to total
generation capacity of inverter.
SolShare underside view
Each output gland will correspond to the output of an L1 and L2 cable,
corresponding to the solar supply for two units. The leftmost membrane
gland corresponds to the solar input.