13
IN (N) OUT (N)
IN (L1) IN (L2)
1(L1) 2(L2) 3(L1) 4(L2) 5(L1) 6(L2) 7(L1) 8(L2) 9(L1) 10(L2)
SOLAR INPUT
OUTPUT 1-2
OUTPUT 3-4
5-6
7-8
9-10
NEUTRALS
INPUTS
OUTPUTS
ONLY CONNECT THE
EARTH CABLES OF
THE INPUT AND FIRST
OUTPUT
AC OUTPUT (NEUTRAL)
IS NOT BONDED TO
GROUND.
Terminal block - Neutral & Phase connections
Conductors
from 12 AWG (4mm2) to 4 AWG (25mm2)
Stripping length
14mm
Tightening torque
18 lb-in (2Nm)
Earth Connection
Please refer to Appendix (p19) for Conductor Specification options.
1. Run input earth from inverter and connect to the SolShare’s earth bar (as shown above)
2. Run output earth cable from earth point in meter panel and connect to the SolShare’s earth bar (as shown above).
Warning:
Only one earth output should be wired from SolShare to meter panel.
Tightening Torque - IN-LBS (N.m)
Conductor size
Attachment method / Bare wire / Termial / Lug / Ferrule
14 AWG - 10 AWG
35 [4.0]
8 AWG
40 [4.5]
6 AWG - 4 AWG
50 [5.6]