background image

506271-01

Page 9  of  14

Issue 0921

Manifold Gas Pressure Adjustment Regulator – Natural
Gas

For purpose of input adjustment, the minimum
permissible gas supply pressure is 5" w.c. for natural gas.

Gas input must never exceed the input capacity shown on
the rating plate. 

 The furnace is equipped for natural gas

rated inputs with manifold pressure of 3.5" w.c.

The manifold pressure can be measured by shutting off the
gas, removing the pipe plug in the downstream side of the
gas valve, and connecting a water manometer or gauge.

Under no circumstances should the final manifold
pressure vary more than 0.3" w.c. from the above
specified pressures. 

 To adjust the regulator, turn the

adjusting screw on the regulator clockwise to increase
pressure and input or counterclockwise to decrease pressure
and input.  See Figure 8 to assist in locating the regulator on
the gas valve.

Check the furnace rate by observing the gas meter, making
sure all other gas appliances are turned off.  The test hand on
the meter should be timed for at least one revolution, noting
the number of seconds per revolution.

 

 The heating value of

the gas can be obtained from the local utility.

x

 

3600

 

x

=

Cubic Feet Per Revolution

BTU/HR
 INPUT

 # Seconds Per Revolution

Heating

Value

the hand on the 1-cubic foot dial to make a revolution with a
100,000 BTU/HR furnace running. The result is 99,750 BTU/
HR, which is close to the 100,000 BTU/HR rating of the
furnace.

Manifold Gas Pressure Adjustment Regulator –
LPG/Propane Gas

LPG/propane units require a regulator, and a regulator on
the LPG/propane tank is also required.

For purpose of input adjustment, the minimum
permissible gas supply pressure (inlet side of gas valve)
is 11" w.c. for LPG/propane.

If at any time ignition is slow and burner does not seem to
be operating correctly, check manifold pressure (outlet side
of the gas valve). 

It should be 10" to 10.5" w.c. pressure

for LPG/propane.

The furnace is designed to obtain rated input at 10" w.c.
manifold pressure for propane.

Example:

 By actual measurement, it takes 38 seconds for

To check this pressure:

1.

Turn off gas valve.

2.

Remove plug on valve marked “OUTLET PRESSURE.”

3.

Install a water manometer.

4.

Turn on gas valve and initiate a call for heat. If manifold
pressure must be adjusted, remove cap from pressure
regulator and turn adjustment screw clockwise to
increase pressure or counterclockwise to reduce
pressure.

5.

After checking pressure, turn gas off, remove
manometer fitting, and replace pipe plug and regulator
cap.

6.

Put furnace in operation and check plug for leaks using
soapy solution.

Burner and Burner Orifice Instructions

To check or change burners or burner orifices:

1.

Close the main manual gas shutoff valve and turn
off all power to unit.

2.

Remove the burner access panel.

3.

Disconnect the union in the gas supply line upstream of
the gas valve and downstream of the manual shutoff
valve.

4.

Label wires going to the gas valve, then disconnect the
wires.

5.

To change orifice:
a.

Remove 4 screws that fasten the manifold to the

burner box assembly and remove the manifold.
b.

Remove the orifices, then install replacement

orifices.
c.

To reassemble:  Reverse above steps, making sure

orifices are inserted into the orifice holders on the back
end of the burners, and that burners are level and
centered on each burner opening in the vest panel.

6.

To remove or service burners:
a.

Label and disconnect the wires to the rollout switch

and disconnect the igniter and flame sensor leads at
the ignition control.
b.

Remove the 4 screws that secure the burner box

assembly to the vest panel and remove the assembly
from the unit.
c.

Remove the 6 screws that fasten the burner rack

and bottom shield assembly to the burner box.  Burners
are now accessible for removal.
d.

To Reassemble:  Reverse above steps.

Summary of Contents for 506271-01

Page 1: ...also be followed Failure to do so may result in equipment damage personal injury and improper performance of the unit WARNING The installation of the furnace wiring warm air ducts venting etc must con...

Page 2: ...from water 2 Condenser coils must have an unlimited supply of air 3 For ground level installation use a level prefabricated pad or use a level concrete slab Do not tie the slab to the building founda...

Page 3: ...r shrubs to obstruct condenser air discharge outlet combustion air inlet or vent outlet Before lifting a unit make sure that the weight is distributed equally on the cables so that it will lift evenly...

Page 4: ...e common venting system 2 Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction leakage corrosion or other deficiencies which could...

Page 5: ...d with the local gas utility For temperature rise of unit see unit rating plate Condensate Drain This package unit is equipped with a 3 4 FPT coupling for condensate line connection Plumbing must conf...

Page 6: ...sure testing of that system at test pressures in excess of 1 2 PSIG 3 48kPa A1 8 N P T plugged tapping accessible for test gauge connections must be installed immediately upstream of the gas supply co...

Page 7: ...l power and control wiring to the unit waterproof type connectors must be used so that water or moisture cannot be drawn into the unit during normal operation CAUTION Compressor Units are shipped with...

Page 8: ...rt Check List After the entire control circuit has been energized and the heating section is operating make the following checks 1 Check for gas leaks using soapy solution in the unit piping as well a...

Page 9: ...correctly check manifold pressure outlet side of the gas valve It should be 10 to 10 5 w c pressure for LPG propane The furnace is designed to obtain rated input at 10 w c manifold pressure for propa...

Page 10: ...fan motor and blower motor Blower Delay Cooling The circulating air blower is controlled by a timing circuit in the integrated blower ignition control Timings are not adjustable Blower ON delay is 5 s...

Page 11: ...s the main gas valve To reset push the button on top of the switch Auxiliary Limit This control is located in the side of the circulation air blower housing The switch opens and shuts off the blower i...

Page 12: ...down the heat exchanger tubes from the flue collector end 7 If soot buildup is excessive remove the vent motor and clean the wheel and housing Run the wire brush down the flue extension at the outlet...

Page 13: ...506271 01 Page 13 of 14 Issue 0921 Wiring Diagram Single Phase Figure 8...

Page 14: ...Page 14 of 14 506271 01 Issue 0921 NOTES...

Reviews: