background image

Page 4  of  14

506271-01

Issue 0921

Minimum horizontal clearance of 4' from electric meters, gas
meters, regulator, and relief equipment is required.

In addition to the above requirements, consideration must
be given to prevent unwanted ice buildup from the vent
condensate.  The vent should not be located on the side of
a building where the prevailing winter winds could trap the
moisture, causing it to freeze on the walls or on overhangs
(under eaves).   The vent location should not discharge over
a sidewalk, patio, or other walkway where the condensate
could cause the surface to become slippery.

The products of combustion must not be allowed to
accumulate within a confined space and recirculate.

Vent Cover

For shipping purposes, the unit is shipped with the vent cover
packaged in the unit supply air compartment.  Retrieve the
vent cover from the supply air compartment.

To attach the vent cover to the unit:

1.

Locate the vent screen. It is packed in the plastic bag
that contains these Installation Instructions.

2.

Remove the two screws that will be used to attach the
screen to the unit (see Figure 2).

3.

Center the screen over the hole and re-insert the screws
removed in Step 2.

4.

Remove the 4 screws that will be used to attach the
vent cover (see Fig. 3).  Install the vent cover using these
screws.  A properly installed vent cover will not extend
above the top of the unit.

Removal of Unit from Common Venting System

When an existing furnace is removed from a common venting
system serving other appliances, the venting system is likely
to be too large to properly vent the remaining attached
appliances.  The following test should be conducted with each
appliance while the other appliances connected to the common
venting system are not in operation.

1.

Seal any unused openings in the common venting
system.

2.

Visually inspect the venting system for proper size and
horizontal pitch and determine there is no blockage or
restriction, leakage, corrosion, or other deficiencies
which could cause an unsafe condition.

3.

Insofar as is practical, close all building doors and
windows between the space in which the appliances
remaining connected to the common venting system are
located and other spaces in the building.  Turn on clothes
dryers and any appliance not connected to the common
venting system.  Turn on exhaust fans, such as range
hoods and bathroom exhausts, so they will operate at
maximum speed.  Do not operate a summer exhaust
fan.  Close fireplace dampers.

4.

Following the lighting instructions, place the unit being
inspected in operation.  Adjust the thermostat so the
appliance will operate continuously.

5.

Test for spillage at the draft control relief opening after 5
minutes of main burner operation.  Use the flame of a
match or candle.

6.

Follow the preceding steps for each appliance connected
to the common venting system.

7.

After it has been determined that each appliance
remaining connected to the common venting system
properly vents when tested as outlined above, return
doors, windows, exhaust fans, fireplace dampers, and
any other fuel burning appliance to their previous
condition of use.

8.

If improper venting is observed during any of the above
tests, the common venting system must be corrected.

See  National Fuel Gas Code, ANSI Z223.1 (latest
edition) or CAN/CGA B149.1 & .2 Canadian
Installation Codes to correct improper operation of
common venting system.

If a gas furnace that’s connected to a common venting system
is being removed when this package unit is installed, then read
and follow the instructions in the “Removal of Unit from
Common Venting System” section that follows.  Otherwise, you

may skip this section.

NOTE:

Installing the Vent Cover

Figure 2

Screen

Screen attachment screws

Vent Cover

Vent Cover
Attachment
Screws
(Plus 2 on 
other side)

Summary of Contents for 506271-01

Page 1: ...also be followed Failure to do so may result in equipment damage personal injury and improper performance of the unit WARNING The installation of the furnace wiring warm air ducts venting etc must con...

Page 2: ...from water 2 Condenser coils must have an unlimited supply of air 3 For ground level installation use a level prefabricated pad or use a level concrete slab Do not tie the slab to the building founda...

Page 3: ...r shrubs to obstruct condenser air discharge outlet combustion air inlet or vent outlet Before lifting a unit make sure that the weight is distributed equally on the cables so that it will lift evenly...

Page 4: ...e common venting system 2 Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction leakage corrosion or other deficiencies which could...

Page 5: ...d with the local gas utility For temperature rise of unit see unit rating plate Condensate Drain This package unit is equipped with a 3 4 FPT coupling for condensate line connection Plumbing must conf...

Page 6: ...sure testing of that system at test pressures in excess of 1 2 PSIG 3 48kPa A1 8 N P T plugged tapping accessible for test gauge connections must be installed immediately upstream of the gas supply co...

Page 7: ...l power and control wiring to the unit waterproof type connectors must be used so that water or moisture cannot be drawn into the unit during normal operation CAUTION Compressor Units are shipped with...

Page 8: ...rt Check List After the entire control circuit has been energized and the heating section is operating make the following checks 1 Check for gas leaks using soapy solution in the unit piping as well a...

Page 9: ...correctly check manifold pressure outlet side of the gas valve It should be 10 to 10 5 w c pressure for LPG propane The furnace is designed to obtain rated input at 10 w c manifold pressure for propa...

Page 10: ...fan motor and blower motor Blower Delay Cooling The circulating air blower is controlled by a timing circuit in the integrated blower ignition control Timings are not adjustable Blower ON delay is 5 s...

Page 11: ...s the main gas valve To reset push the button on top of the switch Auxiliary Limit This control is located in the side of the circulation air blower housing The switch opens and shuts off the blower i...

Page 12: ...down the heat exchanger tubes from the flue collector end 7 If soot buildup is excessive remove the vent motor and clean the wheel and housing Run the wire brush down the flue extension at the outlet...

Page 13: ...506271 01 Page 13 of 14 Issue 0921 Wiring Diagram Single Phase Figure 8...

Page 14: ...Page 14 of 14 506271 01 Issue 0921 NOTES...

Reviews: