10-second interval, then the ignition control will  de-
energize the gas valve.

6.

The ignition control is designed to repeat this “trial for
ignition” a total of three times.  If, at the end of the third
trial, flame still has not been established, then the ignition
control will try to light again 1 hour later.  The 1-hour
retry is indefinite.  The ignition control can be reset by
interrupting the unit power or the thermostat circuit.

7.

When the thermostat is satisfied, the draft motor and
gas valve are de-energized. The blower motor will
continue to run for a short period after the furnace is
shut down.

Blower Delay – Heating

The on/off delay of the circulating air blower is controlled by
a timing circuit in the integrated ignition control. Timings are
not adjustable.  The blower “ON” delay is 30 seconds after
the burners are lit and the blower “OFF” timing is 120
seconds after shutting down the burners.

Safety Controls

The control circuit includes the following safety controls:

Limit Control  

This control is located inside the heating

compartment and is designed to open at abnormally high
circulating air temperatures.  It resets automatically.  The limit
control operates when a high temperature condition, caused
by inadequate airflow, occurs.  This closes the main gas valve,
and the circulation air blower continues to operate in this
situation.

Pressure Switch  

If the draft motor should fail, the pressure

switch prevents the spark electrode and gas valve from being
energized.

Flame Sensor   

If the ignition control does not receive a

signal from the flame sensor indicating that the burners have
established flame, the main gas valve closes after the 10-
second trial for ignition period.

Rollout Switch   

The switch is located on the left side of

burner box.  In the event of a sustained main burner rollout,
the rollout switch shuts off the ignition control and closes
the main gas valve.  To reset, push the button on top of the
switch.

Auxiliary Limit  

This control is located in the side of the

circulation air blower housing.  The switch opens and shuts
off the blower/ignition control and closes the main gas valve
should the circulation blower fail to operate.  This control
resets automatically.

High Altitude

The input rate shown on the rating plate is for elevations up
to 2000 feet.  For elevations from 2001 to 4500 feet, the
input rate is reduced by 5%. For elevations above 4500 feet,
refer to the National Fuel Gas Code Z223.1 (latest edition)
or the Canadian Installation Codes CAN/CGA-B149.1 &
B149.2 for further details.

Secure Owner’s Approval

When the system is functioning properly, secure the owner’s
approval.  Show the owner the location of all disconnect
switches and the thermostat. Instruct the owner on how to
start and stop the unit and how to adjust temperature settings
within the limitations of the system.

Periodic inspection and maintenance normally consists of
changing or cleaning the filters and cleaning the outdoor
coil.  On occasion, other components of the furnace may
also require cleaning.

MAINTENANCE

Filters

Filters are not supplied with the unit. Inspect once a month.
Replace disposable or clean permanent type as necessary.

Do not replace permanent type with disposable.

Motors

Indoor and outdoor fan and vent motors are permanently
lubricated and require no maintenance.

Outdoor Coil

Dirt and debris should not be allowed to accumulate on the
outdoor coil surface or other parts in the air circuit.  Cleaning
should be as often as necessary to keep coil clean.  Use a
brush, vacuum cleaner attachment, or other suitable means.
If water is used to clean the coil, be sure the power to unit is
shut off prior to cleaning.  

Care should be used when

cleaning the coil so that the coil fins are not damaged.
Do not permit the hot condenser air discharge to be
obstructed by overhanging structures or shrubs.

Shut off all electrical power to the unit before conducting
any maintenance procedures.  Failure to do so could
cause personal injury.

  WARNING

Summary of Contents for 506271-01

Page 1: ...also be followed Failure to do so may result in equipment damage personal injury and improper performance of the unit WARNING The installation of the furnace wiring warm air ducts venting etc must con...

Page 2: ...from water 2 Condenser coils must have an unlimited supply of air 3 For ground level installation use a level prefabricated pad or use a level concrete slab Do not tie the slab to the building founda...

Page 3: ...r shrubs to obstruct condenser air discharge outlet combustion air inlet or vent outlet Before lifting a unit make sure that the weight is distributed equally on the cables so that it will lift evenly...

Page 4: ...e common venting system 2 Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction leakage corrosion or other deficiencies which could...

Page 5: ...d with the local gas utility For temperature rise of unit see unit rating plate Condensate Drain This package unit is equipped with a 3 4 FPT coupling for condensate line connection Plumbing must conf...

Page 6: ...sure testing of that system at test pressures in excess of 1 2 PSIG 3 48kPa A1 8 N P T plugged tapping accessible for test gauge connections must be installed immediately upstream of the gas supply co...

Page 7: ...l power and control wiring to the unit waterproof type connectors must be used so that water or moisture cannot be drawn into the unit during normal operation CAUTION Compressor Units are shipped with...

Page 8: ...rt Check List After the entire control circuit has been energized and the heating section is operating make the following checks 1 Check for gas leaks using soapy solution in the unit piping as well a...

Page 9: ...correctly check manifold pressure outlet side of the gas valve It should be 10 to 10 5 w c pressure for LPG propane The furnace is designed to obtain rated input at 10 w c manifold pressure for propa...

Page 10: ...fan motor and blower motor Blower Delay Cooling The circulating air blower is controlled by a timing circuit in the integrated blower ignition control Timings are not adjustable Blower ON delay is 5 s...

Page 11: ...s the main gas valve To reset push the button on top of the switch Auxiliary Limit This control is located in the side of the circulation air blower housing The switch opens and shuts off the blower i...

Page 12: ...down the heat exchanger tubes from the flue collector end 7 If soot buildup is excessive remove the vent motor and clean the wheel and housing Run the wire brush down the flue extension at the outlet...

Page 13: ...506271 01 Page 13 of 14 Issue 0921 Wiring Diagram Single Phase Figure 8...

Page 14: ...Page 14 of 14 506271 01 Issue 0921 NOTES...

Reviews: