The supply and return air duct systems should be designed
for the CFM and static requirements of the job. 

 They should

not be sized by matching the dimensions of the duct
connections on the unit.
Filters

Filters are not supplied with the unit.  Filters must always be
installed ahead of the evaporator coil and must be kept clean
or replaced.  Dirty filters will reduce the airflow of the unit.
Filters should be sized in accordance with Table 3.

This unit is equipped with an internal filter clip which is located
in the indoor coil compartment attached to the side of the
unit drain pan.

Gas Piping

Proper sizing of a gas piping depends on the cubic feet per
hour of gas flow required, specific gravity of the gas, and
length of run.  National Fuel Gas Code Z223.1 latest edition
should be followed in all cases unless superseded by local
codes or gas company requirements.  In Canada, refer to
CAN/CGA B.149.1 & .2 (latest edition).

The heating value of the gas may differ with locality.  The
value should be checked with the local gas utility.  For
temperature rise of unit, see unit rating plate.

Condensate Drain

This package unit is equipped with a 3/4" FPT coupling for
condensate line connection. Plumbing must conform to local
codes.  Use a sealing compound on male pipe threads.

The condensate drain line must be properly trapped and
routed to a suitable drain.

 See Figure 3 for proper drain

arrangement.  The drain line must pitch to an open drain or
pump to prevent clogging of the line.  Seal around the drain
connection with suitable material to prevent air leakage into
the return air system.

Ductwork

Ductwork should be designed and sized according to the
methods in Manual Q of the Air Conditioning Contractors of
America (ACCA).

A closed return duct system shall be used.  This shall not
preclude use of economizers or outdoor fresh air intake.  It
is recommended that supply and return duct connections at
the unit be made with flexible joints.

When fastening ductwork to the side duct flanges on unit,
insert screws through duct flanges only.  Do not insert
screws through the casing.  Outdoor ductwork must be
insulated and waterproofed.

 CAUTION

Table 2

Minimum Required Surface Area

for Disposable Filters

Typical Condensate Drain Connection

Figure 3

Summary of Contents for 506271-01

Page 1: ...also be followed Failure to do so may result in equipment damage personal injury and improper performance of the unit WARNING The installation of the furnace wiring warm air ducts venting etc must con...

Page 2: ...from water 2 Condenser coils must have an unlimited supply of air 3 For ground level installation use a level prefabricated pad or use a level concrete slab Do not tie the slab to the building founda...

Page 3: ...r shrubs to obstruct condenser air discharge outlet combustion air inlet or vent outlet Before lifting a unit make sure that the weight is distributed equally on the cables so that it will lift evenly...

Page 4: ...e common venting system 2 Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction leakage corrosion or other deficiencies which could...

Page 5: ...d with the local gas utility For temperature rise of unit see unit rating plate Condensate Drain This package unit is equipped with a 3 4 FPT coupling for condensate line connection Plumbing must conf...

Page 6: ...sure testing of that system at test pressures in excess of 1 2 PSIG 3 48kPa A1 8 N P T plugged tapping accessible for test gauge connections must be installed immediately upstream of the gas supply co...

Page 7: ...l power and control wiring to the unit waterproof type connectors must be used so that water or moisture cannot be drawn into the unit during normal operation CAUTION Compressor Units are shipped with...

Page 8: ...rt Check List After the entire control circuit has been energized and the heating section is operating make the following checks 1 Check for gas leaks using soapy solution in the unit piping as well a...

Page 9: ...correctly check manifold pressure outlet side of the gas valve It should be 10 to 10 5 w c pressure for LPG propane The furnace is designed to obtain rated input at 10 w c manifold pressure for propa...

Page 10: ...fan motor and blower motor Blower Delay Cooling The circulating air blower is controlled by a timing circuit in the integrated blower ignition control Timings are not adjustable Blower ON delay is 5 s...

Page 11: ...s the main gas valve To reset push the button on top of the switch Auxiliary Limit This control is located in the side of the circulation air blower housing The switch opens and shuts off the blower i...

Page 12: ...down the heat exchanger tubes from the flue collector end 7 If soot buildup is excessive remove the vent motor and clean the wheel and housing Run the wire brush down the flue extension at the outlet...

Page 13: ...506271 01 Page 13 of 14 Issue 0921 Wiring Diagram Single Phase Figure 8...

Page 14: ...Page 14 of 14 506271 01 Issue 0921 NOTES...

Reviews: