background image

Page 12  of  14

506271-01

Issue 0921

Burners

To clean the burners, first remove them from the furnace as
explained in Burner Instructions on page 9.  Vacuum and/or
brush as required.

Vent Outlet

Visually inspect vent outlet periodically to make sure that there
is no buildup of soot or dirt.  If necessary, clean to maintain
adequate opening to discharge flue products.

Heat Exchanger

With proper combustion adjustment, the heat exchanger of a
gas-fired furnace will seldom need cleaning.  Sooting of a gas
appliance is highly irregular and once cleaned, the cause of
the sooting must be determined.  If the heat exchanger should
become sooted, it can be cleaned as follows:

1.

Remove the burner assembly as outlined in Burner
Instructions on page 9.

2.

Remove the combustion blower.

3.

At the bottom of the heating section, remove the screws
holding the flue collector box.   Carefully remove the flue
collector box without ripping the adjacent insulation.

4.

Using a wire brush on a flexible wand, brush out the
inside of each heat exchanger from the burner inlet and
flue outlet ends.

5.

Brush out the inside of the flue collector box.

6.

Run the wire brush down the heat exchanger tubes from
the flue collector end.

7.

If soot buildup is excessive, remove the vent motor and
clean the wheel and housing.  Run the wire brush down
the flue extension at the outlet of the vent housing.

8.

After brushing is complete, blow all brushed areas with
air. Vacuum as needed.

9.

Replace parts in the reverse order they were removed
in Steps 1 through 3.

10. When replacing the flue collector box, be careful so as

not to tear the adjoining insulation.

11. Assure that all joints on the vent side of the combustion

system are air tight.  Apply a high temperature (+500°F)
sealing compound where needed.

CONTROL SYSTEM DIAGNOSTICS

Fault Codes

Table 4

LED Status

Flashing Rate

     Fault
Description

Slow Flash

Fast Flash

2 Flash

3 Flash

4 Flash

5 Flash

Steady

 One flash
per second

Normal operaton:
No call for heat

Two flashes
per second

Normal operation:
Call for heat

   Two flashes
 in second with
1-second pause

Internal failure:
Micro-controller
failure; self-check

Five flashes in
2.5 seconds with
1-second pause

Flame sensed
and gas valve
not energized

Four flashes in
2 seconds with
1-second pause

High limit or
rollout switch
open

Three flashes in
1.5 seconds with
1-second pause

Pressure switch
senses incorrect
pressure or auxiliary
limit is open, or gas
valve coil is open.

System lockout:
Failed to detect
or sustain flame

--

Summary of Contents for 506271-01

Page 1: ...also be followed Failure to do so may result in equipment damage personal injury and improper performance of the unit WARNING The installation of the furnace wiring warm air ducts venting etc must con...

Page 2: ...from water 2 Condenser coils must have an unlimited supply of air 3 For ground level installation use a level prefabricated pad or use a level concrete slab Do not tie the slab to the building founda...

Page 3: ...r shrubs to obstruct condenser air discharge outlet combustion air inlet or vent outlet Before lifting a unit make sure that the weight is distributed equally on the cables so that it will lift evenly...

Page 4: ...e common venting system 2 Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction leakage corrosion or other deficiencies which could...

Page 5: ...d with the local gas utility For temperature rise of unit see unit rating plate Condensate Drain This package unit is equipped with a 3 4 FPT coupling for condensate line connection Plumbing must conf...

Page 6: ...sure testing of that system at test pressures in excess of 1 2 PSIG 3 48kPa A1 8 N P T plugged tapping accessible for test gauge connections must be installed immediately upstream of the gas supply co...

Page 7: ...l power and control wiring to the unit waterproof type connectors must be used so that water or moisture cannot be drawn into the unit during normal operation CAUTION Compressor Units are shipped with...

Page 8: ...rt Check List After the entire control circuit has been energized and the heating section is operating make the following checks 1 Check for gas leaks using soapy solution in the unit piping as well a...

Page 9: ...correctly check manifold pressure outlet side of the gas valve It should be 10 to 10 5 w c pressure for LPG propane The furnace is designed to obtain rated input at 10 w c manifold pressure for propa...

Page 10: ...fan motor and blower motor Blower Delay Cooling The circulating air blower is controlled by a timing circuit in the integrated blower ignition control Timings are not adjustable Blower ON delay is 5 s...

Page 11: ...s the main gas valve To reset push the button on top of the switch Auxiliary Limit This control is located in the side of the circulation air blower housing The switch opens and shuts off the blower i...

Page 12: ...down the heat exchanger tubes from the flue collector end 7 If soot buildup is excessive remove the vent motor and clean the wheel and housing Run the wire brush down the flue extension at the outlet...

Page 13: ...506271 01 Page 13 of 14 Issue 0921 Wiring Diagram Single Phase Figure 8...

Page 14: ...Page 14 of 14 506271 01 Issue 0921 NOTES...

Reviews: