background image

506271-01

Page 1  of  14

Issue 0921

Save these instructions for future reference

INSTALLATION INSTRUCTIONS

RPGE/RGE Series

Gas Heating/Electric Cooling Package Unit

Do not store combustible materials, including gasoline
and other flammable vapors and liquids, near the furnace,
vent pipe, or warm air ducts.  Such actions could cause
property damage, personal injury, or death.

  WARNING

Improper installation, adjustment, alteration, service, or maintenance can cause injury or property damage.
Refer to this manual.  For assistance or additional information, consult a qualified installer, service agency,
or the gas supplier.

 

WARNING

Never use a flame to check for gas leaks.  Explosion
causing injury or death may occur.

  WARNING

If this unit is to be installed in a mobile or manufactured
home application, the ductwork must be sized to achieve
static pressures within the manufacturer’s guidelines.   All
other installation guidelines must also be followed.  Failure
to do so may result in equipment damage, personal injury,
and improper performance of the unit.

  WARNING

The installation of the furnace, wiring, warm air ducts, venting, etc. must conform to the requirements of the National Fire
Protection Association; the National Fuel Gas Code, ANSI Z223.1 (latest edition) and the National Electrical Code, ANSI/
NFPA No. 70 (latest edition) in the United States; the Canadian Installation Codes CAN/CGA-B149.1 & .2 (latest edition)
and the Canadian Electrical Code Part 1, CSA 22.1 (latest edition) in Canada; and any state or provincial laws, local
ordinances, or local gas utility requirements.  Local authorities having jurisdiction should be consulted before installation
is made.  Such applicable regulations or requirements take precedence over the general instructions in this manual.

 CAUTION

Manufactured By

Allied Air Enterprises, Inc.

A Lennox International Company

215 Metropolitan Drive

West Columbia, SC  29170

TABLE OF CONTENTS

INSTALLATION ...................................... 2

START-UP .............................................. 8

OPERATION ........................................ 10

Cooling System ............................... 10
Heating System............................... 10

MAINTENANCE .................................... 11

CONTROL SYSTEM DIAGNOSTICS .. 12

WIRING DIAGRAM .............................. 13

*506271-01*

Summary of Contents for 506271-01

Page 1: ...also be followed Failure to do so may result in equipment damage personal injury and improper performance of the unit WARNING The installation of the furnace wiring warm air ducts venting etc must con...

Page 2: ...from water 2 Condenser coils must have an unlimited supply of air 3 For ground level installation use a level prefabricated pad or use a level concrete slab Do not tie the slab to the building founda...

Page 3: ...r shrubs to obstruct condenser air discharge outlet combustion air inlet or vent outlet Before lifting a unit make sure that the weight is distributed equally on the cables so that it will lift evenly...

Page 4: ...e common venting system 2 Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction leakage corrosion or other deficiencies which could...

Page 5: ...d with the local gas utility For temperature rise of unit see unit rating plate Condensate Drain This package unit is equipped with a 3 4 FPT coupling for condensate line connection Plumbing must conf...

Page 6: ...sure testing of that system at test pressures in excess of 1 2 PSIG 3 48kPa A1 8 N P T plugged tapping accessible for test gauge connections must be installed immediately upstream of the gas supply co...

Page 7: ...l power and control wiring to the unit waterproof type connectors must be used so that water or moisture cannot be drawn into the unit during normal operation CAUTION Compressor Units are shipped with...

Page 8: ...rt Check List After the entire control circuit has been energized and the heating section is operating make the following checks 1 Check for gas leaks using soapy solution in the unit piping as well a...

Page 9: ...correctly check manifold pressure outlet side of the gas valve It should be 10 to 10 5 w c pressure for LPG propane The furnace is designed to obtain rated input at 10 w c manifold pressure for propa...

Page 10: ...fan motor and blower motor Blower Delay Cooling The circulating air blower is controlled by a timing circuit in the integrated blower ignition control Timings are not adjustable Blower ON delay is 5 s...

Page 11: ...s the main gas valve To reset push the button on top of the switch Auxiliary Limit This control is located in the side of the circulation air blower housing The switch opens and shuts off the blower i...

Page 12: ...down the heat exchanger tubes from the flue collector end 7 If soot buildup is excessive remove the vent motor and clean the wheel and housing Run the wire brush down the flue extension at the outlet...

Page 13: ...506271 01 Page 13 of 14 Issue 0921 Wiring Diagram Single Phase Figure 8...

Page 14: ...Page 14 of 14 506271 01 Issue 0921 NOTES...

Reviews: