background image

506469-01

Issue  1008

4.  Remover the existing R-22 refrigerant flow control orifice
or thermal expansion valve before continuing with flushing
procedures.  R-22 flow control devices are not approved for
use with R410A refrigerant and may prevent proper flushing.
Use a field-provided fitting to reconnect the lines.

5.  Remove the pressure tap valve cores from the 4AC18LT
units service valves.  Connect an R-22 cylinder with clean
refrigerant to the suction service valve.  Connect the R-22
gauge set to the liquid line valve and connect a recovery
maching with an empty recovery tank to the gauge set.

6.  Set the recovery machine for liquid recovery and start
the recovery machine.  Open the gauge set valves to allow
the recovery machine to pull a vacuum on the existing system
line set and indoor coil.

7.  Invert the cylinder of clean R-22 and open its valve to
allow liquid refrigerant to flow in to the system through the
suction line valve.  Allow the refrigerant to pass from the
cylinder and through the line set and the indoor coil before it
enters the recovery machine.

8.  After all of the liquid refrigerant has been recovered, switch
the recovery machine to vapor recovery so that all of the R-
22 vapor is recovered.   Allow the recovery machine to pull a
vacuum on the sytem.

NOTE:  

A single system flush should remove all of the mineral

oil from the existing refrigerant lines and indoor coil.  A second
flushing may be done (using clean refrigerant)  if insufficient
amounts of mineral oil were removed during the first flush.

After each system flush, allow the recovery machine to
pull a vacuum on the system at the end of the procedure.

9.  Close the valve on the inverted R-22 cylinder and the
gauge set valves.  Pump the remaining refrigerant out of
the recovery machine and turn the machine off.

10.  Use nitrogen to break the vacuum on the refrigerant
lines and indoor coil before removing the recovery machine,
gauges, and R-22 refrigerant drum.  Re-install pressure tap
valve cores into the 4AC18LT unit’s service valves.

11.  Install the fixed orifice (or thermal expansion valve
approved for use with R410A refrigerant) in the liquid line at
the indoor coil.

Refrigerant Metering Device

4AC18LT units are designed for use with TXV systems.
Refer to the appropriate following section for information on
installing the chosen refrigerant metering device.

An R410A system will not operate properly with an R-22
metering device.

Install the refrigerant metering device as shown in Figure
10.  Do not twist cap tubes when loosening the seal nut
from the orifice housing.  Use wrench to back up the
distributor.

Expansion Valve Systems

Expansion valves equipped with Chatleff-type fittings are
available from the manufacturer.  See Table 4 for proper
TXV for each unit.

To install an expansion valve (See Figure 10 above):

1.  Separate the distributor assembly and remove the piston
orifice and used teflon seal.  Insert nozzle end of the
expansion valve along with a new teflon seal into the
distributor and tighten  to 20 - 30 ft. lbs.  Use backup wrench
on all wrench flats.  

Overtightening will crush the teflon

seal and may cause a leak.

2.  Attach liquid line portion of distributor assembly along
with new teflon seal to the inlet of the expansion valve.
Tighten to 20 - 30 ft. lbs.  Use backup wrench on all wrench
flats.  

Overtightening will crush the teflon seal and may

cause a leak.

Page 9 of  24

Figure 10

Table 4

TXV Data

MODEL

PART NUMBER

4AC18LT- 24, -36

H4TXV01

4AC18LT - 48, -60

H4TXV03

Summary of Contents for 4AC18LT Series

Page 1: ...cal shock Disconnect all remote power supplies before installing or servicing any portion of the system Failure to disconnect power supplies can result in property damage personal injury or death WARN...

Page 2: ...qualified personnel and do not supersede any national or local codes in any way The installation must comply with all provincial state and local codes as well as the National Electrical Code U S or C...

Page 3: ...s will prevent ice from building up under the unit during a defrost cycle Refer to following roof mounting section for barrier construction if unit must face prevailing winter winds If unit coil canno...

Page 4: ...dation and the introduction of moisture into the system 3 Use silver alloy brazing rods 5 or 6 silver alloy for copper to copper brazing or 45 silver alloy for copper to brass or copper to steel brazi...

Page 5: ...ctionable noise when vibration is translated into sound As a result more energy or vibration can be expected Close attention to line set isolation must be observed Following are some points to conside...

Page 6: ...be sure to empty all existing traps Residual mineral oil can act as an insulator preventing proper heat transfer It can also clog thethermalexpansionvalve reducingsystemperformance and capacity Failu...

Page 7: ...nt lines must not contact structure Refrigeraant Line Sets Installing Vertical Runs new construction shown NOTE Similar installation practices should be used if line set is to be installed on exterior...

Page 8: ...sting system Refer to the gauges after shutdown to confirm that the entire system is completely void of refrigerant Disconnect the liquid and suction lines from the existing outdoor unit If the existi...

Page 9: ...dure 9 Close the valve on the inverted R 22 cylinder and the gauge set valves Pump the remaining refrigerant out of the recovery machine and turn the machine off 10 Use nitrogen to break the vacuum on...

Page 10: ...seal To Access the Schrader Port 1 Remove the service port cap with an adjustable wrench 2 Connect gauge to the service port 3 When testing is completed replace service port cap Tighten finger tight t...

Page 11: ...ant requirements will vary with lenths Check all joints for leaks Purge nitrogen and R410A mixture Correct any leaks and rechecks Evacuation Evacuating the system of noncondensables is critical for pr...

Page 12: ...r port hose to a nitrogen cylinder with pressure regulator set to 150 psig and purge the hose Open the manifold gauge valves to break the vacuum in the line set and indoor unit Close the manifold gaug...

Page 13: ...g plate This charge is based on a matching indoor coil and outdoor coil with 15 line set For varying lengths of line set refer to Table 5 for refrigerant charge adjustment A blank space is provided on...

Page 14: ...nter manifold hose to an upright cylinder of R410A 3 If room temperature is below 70 F set the room thermostat to call for heat This will create the necessary load for properly charging the system in...

Page 15: ...P ressure P sig T em p F P ressure P sig 32 100 8 74 214 0 116 396 0 33 102 9 75 217 4 117 401 3 34 105 0 76 220 9 118 406 7 35 107 1 77 224 4 119 412 2 36 109 2 78 228 0 120 417 7 37 111 4 79 231 6...

Page 16: ...506469 01 Issue 1008 Page 16 of 24 Table 8...

Page 17: ...will flash a number of times consecutively pause and then repeat the process To identify a flash code number count the number of consecutive flashes Refer to Table 9 on page 18 and Table 10 on page 1...

Page 18: ...506469 01 Issue 1008 Page 18 of 24 Table 9 Flash Codes...

Page 19: ...506469 01 Issue 1008 Page 19 of 24 Table 10 Flash Codes cont...

Page 20: ...506469 01 Issue 1008 Page 20 of 24 Table 11 Miswired Module Troubleshooting...

Page 21: ...nsufficient cooling the unit should be gauged and refrigerant charge checked Refer to the Refrigerant Charging section on page 12 Indoor Coil 1 Clean coil if necessary 2 Check connecting lines and coi...

Page 22: ...Rated Load Ampacity _________ Compressor Amperage ________ Outdoor Fan __________ Maximum Fuse or Circuit Breaker ________________________ Electical Connections Tight Indoor Filter Clean Supply Volta...

Page 23: ...506469 01 Issue 1008 Page 23 of 24 WIRE DIAGRAM...

Page 24: ...506469 01 Issue 1008 Page 24 of 24 NOTES...

Reviews: