background image

506469-01

Issue  1008

Using an Electronic Leak Detector

1.  Connect the high pressure hose of the manifold gauge
set to the suction valve service port.  (Normally the high
pressure hose is connected to the liquid line port; however,
connecting it to the suction ports helps to protect the manifold
gauge set from damage caused by high pressure.)

2.  With both manifold valves closed, connect the cylinder of
R410A refrigerant.  Open the valve on the R410A cylinder
(vapor only).

3.  Open the high pressure side of the manifold to allow
R410A into the line set and indoor unit.  Weigh in a trace
amount of R410A.  (A trace amount is a maximum of 2 oz.
of refrigerant or 3 lbs. pressure.)  Close the valve on the
R410A cylinder and the valve on the high pressure side of
the manifold gauge set.  Disconnect the R410A cylinder.

4.  Connect a cylinder of nitrogen with a pressure regulating
valve to the center port of the manifold gauge set.  

When

using high pressure gas such as nitrogen for this
purpose, be sure to use a regulator that can control the
pressure down to 1 or 2 psig.

5.  Adjust nitrogen pressure to 150 psig.  Open the valve on
the high side of the manifold gauge set to pressurize the
line set and the indoor coil.

6.  After a short period of time, open a refrigerant port to
make sure that an adequate amount of refrigerant has been
added for detection (refrigerant requirements will vary with
lenths).  Check all joints for leaks.  Purge nitrogen and R410A
mixture.  Correct any leaks and rechecks.

Evacuation

Evacuating the system of noncondensables is critical for
proper operation of the unit.  Noncondensables are defined
as any gas that will not condense under temperatures and
pressures present during operation of an air conditioning
system.  Noncondensables and water vapor combine with
refrigerant to produce substances that corrode copper piping
and compressor parts.

Use a thermocouple or thermistor electronic vacuum gauge
that is calibrated in microns.  Use an instrument that reads
down to 50 microns.

1.  Connect the manifold gauge set to the service valve ports
as follows:

•  

Low pressure gauge to suction line service valve

•  

High pressure gauge to liquid line service valve.

2.  Connect micron gauge.

3.  Connect the vacuum pump (with vacuum gauge) to the
center port of the manifold gauge set.

Page 11 of  24

Never use oxygen to pressurize refrigeration or air
conditioning systems.  Oxygen will explode on contact
with oil and could cause personal injury or death.

  WARNING

Refrigerant can be harmful if inhaled.  Refrigerant must
always be used and recovered responsibly.  Incorrect
or irresponsible use of refrigerant can result in personal
injury or death.

  WARNING

Do Not use a compressor to evacuate a system.  Avoid
deep vacuum operation.  Extremely low vacuums can
cause internal arcing and compressor failure.  Danger
of equipment damage.  Damage caused by deep vacuum
operation will void warranty.

  WARNING

Figure 12

Summary of Contents for 4AC18LT Series

Page 1: ...cal shock Disconnect all remote power supplies before installing or servicing any portion of the system Failure to disconnect power supplies can result in property damage personal injury or death WARN...

Page 2: ...qualified personnel and do not supersede any national or local codes in any way The installation must comply with all provincial state and local codes as well as the National Electrical Code U S or C...

Page 3: ...s will prevent ice from building up under the unit during a defrost cycle Refer to following roof mounting section for barrier construction if unit must face prevailing winter winds If unit coil canno...

Page 4: ...dation and the introduction of moisture into the system 3 Use silver alloy brazing rods 5 or 6 silver alloy for copper to copper brazing or 45 silver alloy for copper to brass or copper to steel brazi...

Page 5: ...ctionable noise when vibration is translated into sound As a result more energy or vibration can be expected Close attention to line set isolation must be observed Following are some points to conside...

Page 6: ...be sure to empty all existing traps Residual mineral oil can act as an insulator preventing proper heat transfer It can also clog thethermalexpansionvalve reducingsystemperformance and capacity Failu...

Page 7: ...nt lines must not contact structure Refrigeraant Line Sets Installing Vertical Runs new construction shown NOTE Similar installation practices should be used if line set is to be installed on exterior...

Page 8: ...sting system Refer to the gauges after shutdown to confirm that the entire system is completely void of refrigerant Disconnect the liquid and suction lines from the existing outdoor unit If the existi...

Page 9: ...dure 9 Close the valve on the inverted R 22 cylinder and the gauge set valves Pump the remaining refrigerant out of the recovery machine and turn the machine off 10 Use nitrogen to break the vacuum on...

Page 10: ...seal To Access the Schrader Port 1 Remove the service port cap with an adjustable wrench 2 Connect gauge to the service port 3 When testing is completed replace service port cap Tighten finger tight t...

Page 11: ...ant requirements will vary with lenths Check all joints for leaks Purge nitrogen and R410A mixture Correct any leaks and rechecks Evacuation Evacuating the system of noncondensables is critical for pr...

Page 12: ...r port hose to a nitrogen cylinder with pressure regulator set to 150 psig and purge the hose Open the manifold gauge valves to break the vacuum in the line set and indoor unit Close the manifold gaug...

Page 13: ...g plate This charge is based on a matching indoor coil and outdoor coil with 15 line set For varying lengths of line set refer to Table 5 for refrigerant charge adjustment A blank space is provided on...

Page 14: ...nter manifold hose to an upright cylinder of R410A 3 If room temperature is below 70 F set the room thermostat to call for heat This will create the necessary load for properly charging the system in...

Page 15: ...P ressure P sig T em p F P ressure P sig 32 100 8 74 214 0 116 396 0 33 102 9 75 217 4 117 401 3 34 105 0 76 220 9 118 406 7 35 107 1 77 224 4 119 412 2 36 109 2 78 228 0 120 417 7 37 111 4 79 231 6...

Page 16: ...506469 01 Issue 1008 Page 16 of 24 Table 8...

Page 17: ...will flash a number of times consecutively pause and then repeat the process To identify a flash code number count the number of consecutive flashes Refer to Table 9 on page 18 and Table 10 on page 1...

Page 18: ...506469 01 Issue 1008 Page 18 of 24 Table 9 Flash Codes...

Page 19: ...506469 01 Issue 1008 Page 19 of 24 Table 10 Flash Codes cont...

Page 20: ...506469 01 Issue 1008 Page 20 of 24 Table 11 Miswired Module Troubleshooting...

Page 21: ...nsufficient cooling the unit should be gauged and refrigerant charge checked Refer to the Refrigerant Charging section on page 12 Indoor Coil 1 Clean coil if necessary 2 Check connecting lines and coi...

Page 22: ...Rated Load Ampacity _________ Compressor Amperage ________ Outdoor Fan __________ Maximum Fuse or Circuit Breaker ________________________ Electical Connections Tight Indoor Filter Clean Supply Volta...

Page 23: ...506469 01 Issue 1008 Page 23 of 24 WIRE DIAGRAM...

Page 24: ...506469 01 Issue 1008 Page 24 of 24 NOTES...

Reviews: