background image

506469-01

Issue  1008

Page 1 of  24

The equipment covered in this manual is to be installed by trained and experienced service
and installation technicians. Improper installation, modification, service, or use can cause
electrical shock, fire, explosion, or other conditions which may cause personal injury, death,
or property damage. Use appropriate safety gear including safety glasses and gloves when
installing this equipment.

 

WARNING

Sharp metal edges can cause injury. When installing
the unit, use care to avoid sharp edges.

TABLE OF CONTENTS

INSTALLATION ....................................................2

START-UP .......................................................... 13

OPERATION ...................................................... 17

MAINTENANCE ................................................. 21

CONNECTION DIAGRAM .................................. 23

Risk of electrical shock. Disconnect all remote power
supplies before installing or servicing any portion of the
system. Failure to disconnect power supplies can result
in property damage, personal injury, or death.

  WARNING

Installation and servicing of air conditioning equipment
can be hazardous due to internal refrigerant pressure
and live electrical components. Only trained and
qualified service personnel should install or service this
equipment. Installation and service performed by
unqualified persons can result in property damage,
personal injury, or death.

  WARNING

  WARNING

Manufactured By

Allied Air Enterprises, Inc.

A Lennox International Inc. Company

215 Metropolitan Drive

West Columbia, SC 29170

*506469-01*

Save these instructions for future reference

INSTALLATION AND MAINTENANCE INSTRUCTIONS

4AC18LT SERIES

Split System Air Conditioner

Summary of Contents for 4AC18LT Series

Page 1: ...cal shock Disconnect all remote power supplies before installing or servicing any portion of the system Failure to disconnect power supplies can result in property damage personal injury or death WARN...

Page 2: ...qualified personnel and do not supersede any national or local codes in any way The installation must comply with all provincial state and local codes as well as the National Electrical Code U S or C...

Page 3: ...s will prevent ice from building up under the unit during a defrost cycle Refer to following roof mounting section for barrier construction if unit must face prevailing winter winds If unit coil canno...

Page 4: ...dation and the introduction of moisture into the system 3 Use silver alloy brazing rods 5 or 6 silver alloy for copper to copper brazing or 45 silver alloy for copper to brass or copper to steel brazi...

Page 5: ...ctionable noise when vibration is translated into sound As a result more energy or vibration can be expected Close attention to line set isolation must be observed Following are some points to conside...

Page 6: ...be sure to empty all existing traps Residual mineral oil can act as an insulator preventing proper heat transfer It can also clog thethermalexpansionvalve reducingsystemperformance and capacity Failu...

Page 7: ...nt lines must not contact structure Refrigeraant Line Sets Installing Vertical Runs new construction shown NOTE Similar installation practices should be used if line set is to be installed on exterior...

Page 8: ...sting system Refer to the gauges after shutdown to confirm that the entire system is completely void of refrigerant Disconnect the liquid and suction lines from the existing outdoor unit If the existi...

Page 9: ...dure 9 Close the valve on the inverted R 22 cylinder and the gauge set valves Pump the remaining refrigerant out of the recovery machine and turn the machine off 10 Use nitrogen to break the vacuum on...

Page 10: ...seal To Access the Schrader Port 1 Remove the service port cap with an adjustable wrench 2 Connect gauge to the service port 3 When testing is completed replace service port cap Tighten finger tight t...

Page 11: ...ant requirements will vary with lenths Check all joints for leaks Purge nitrogen and R410A mixture Correct any leaks and rechecks Evacuation Evacuating the system of noncondensables is critical for pr...

Page 12: ...r port hose to a nitrogen cylinder with pressure regulator set to 150 psig and purge the hose Open the manifold gauge valves to break the vacuum in the line set and indoor unit Close the manifold gaug...

Page 13: ...g plate This charge is based on a matching indoor coil and outdoor coil with 15 line set For varying lengths of line set refer to Table 5 for refrigerant charge adjustment A blank space is provided on...

Page 14: ...nter manifold hose to an upright cylinder of R410A 3 If room temperature is below 70 F set the room thermostat to call for heat This will create the necessary load for properly charging the system in...

Page 15: ...P ressure P sig T em p F P ressure P sig 32 100 8 74 214 0 116 396 0 33 102 9 75 217 4 117 401 3 34 105 0 76 220 9 118 406 7 35 107 1 77 224 4 119 412 2 36 109 2 78 228 0 120 417 7 37 111 4 79 231 6...

Page 16: ...506469 01 Issue 1008 Page 16 of 24 Table 8...

Page 17: ...will flash a number of times consecutively pause and then repeat the process To identify a flash code number count the number of consecutive flashes Refer to Table 9 on page 18 and Table 10 on page 1...

Page 18: ...506469 01 Issue 1008 Page 18 of 24 Table 9 Flash Codes...

Page 19: ...506469 01 Issue 1008 Page 19 of 24 Table 10 Flash Codes cont...

Page 20: ...506469 01 Issue 1008 Page 20 of 24 Table 11 Miswired Module Troubleshooting...

Page 21: ...nsufficient cooling the unit should be gauged and refrigerant charge checked Refer to the Refrigerant Charging section on page 12 Indoor Coil 1 Clean coil if necessary 2 Check connecting lines and coi...

Page 22: ...Rated Load Ampacity _________ Compressor Amperage ________ Outdoor Fan __________ Maximum Fuse or Circuit Breaker ________________________ Electical Connections Tight Indoor Filter Clean Supply Volta...

Page 23: ...506469 01 Issue 1008 Page 23 of 24 WIRE DIAGRAM...

Page 24: ...506469 01 Issue 1008 Page 24 of 24 NOTES...

Reviews: