Steam Requirements
70458301ENR6
70
Figure 27
T473I
Note: Refer to
Table 18
for sizing of steam lines. Piping must also be sized accordingly for length of runs, and
number of elbows.
1
Steam Coil
6
Trap with Built-In Strainer
2
12 in. (305 mm) Riser
7
Vacuum Breaker (Optional)
3
Condensate Return Line from Supply Line
8
18 in. (457 mm) Drop
4
Shut-Off Valve
9
Solenoid Valve (Supplied with machine)
5
Check Valve
10
Union
Model
Steam Pressure
PSI (bar)
Minimum Supply Pipe
Diameter
Steam Trap Size *
Pounds Condensate/Hour
(Kilograms Condensate/Hour)
025/030 Series
80-100 (5.3-6.9)
3/4 in. NPT
134 (60.8)
035 Series
80-100 (5.3-6.9)
3/4 in. NPT
166 (75.3)
T30 Series
80-100 (5.3-6.9)
3/4 in. NPT
110 (49.9)
* Based on100 psi.
Table 18
T473I
1
2
9
5
10
8
7
6
5
6
4
3
RETURN
SUPPLY
10