Exhaust Requirements
70458301ENR6
46
Figure 19
NOTE:
Table 4
represents units with the same vent
size. If multiple vent sizes are used, consult a local
HVAC specialist.
NOTE: Duct clean-out recommended every 6 feet
(183 cm).
TMB2019N
1
Outlet duct diameter = largest duct diameter
based on number of units
2
45° typical
L
K
J
I
H
G
F
E
D
C
B
A
2
1
ONE MANIFOLD ASSEMBLY
Duct
Station
025 and 030 Series
035, 055 and T30 Series
T45 Series
A
6 in. (152 mm)
8 in. (203 mm)
10 in.
(254 mm)
B
10 in.
(254 mm)
12 in. (305 mm)
15 in. (381 mm)
C
12 in. (305 mm)
15 in. (381 mm)
18 in. (457 mm)
D
14 in. (356 mm)
17 in. (432 mm)
21 in. (533 mm)
E
16 in. (406 mm)
19 in. (483 mm)
24 in. (610 mm)
F
18 in. (457 mm)
21 in. (533 mm)
26 in. (660 mm)
G
19 in. (483 mm)
23 in. (584 mm)
28 in. (711 mm)
H
20 in. (508 mm)
24 in. (610 mm)
30 in. (762 mm)
I
22 in. (559 mm)
26 in. (660 mm)
32 in.
(813 mm)
J
23 in. (584 mm)
27 in. (686 mm)
33 in.
(838 mm)
K
24 in. (610 mm)
28 in. (711 mm)
35 in.
(889 mm)
L
25 in. (635 mm)
30 in. (762 mm)
36 in.
(914 mm)
Table 4