10
Rockwell Automation Publication PFLEX-AP005B-EN-P - May 2019
Chapter 1
Drive Selection Considerations
Table 3 - PowerFlex Drive Comparisons (continued)
PowerFlex Drive
700 Standard Cassette
700 Vector Cassette
Series B
753
755
Protection (continued)
Common mode capacitors
Standard
Standard
(1)
Standard
Standard
Safety input:
Torque-off card
—
—
Standard
Standard
Speed monitor
—
—
Optional
Optional
Hardware enable
Standard
Standard
Standard
Standard
EMC filters (internal)
Standard
Standard
Standard
Drive Control Performance and Features
Motor control type:
Induction V/Hz
Standard
Standard
Standard
Standard
Induction sensorless vector
(SVC)
Standard
Standard
Standard
Standard
Induction flux vector (FVC)
—
Standard with
FORCE Technology
Standard with
FORCE Technology
Standard with
FORCE Technology
Synchronous reluctance V/Hz
Standard
Standard
Standard
Standard
Synchronous reluctance SV
—
—
Standard
Standard
Adjustable voltage mode
—
Standard
—
Standard
Operating speed range
120:1
1,000:1
(2)
120:1
(3)
1,000:1
120:1
1,000:1
120:1
Speed control regulation
(% of base speed across
operating speed range)
0.5% across 80:1
0.001% across 120:1
0.1% across 120:1
0.001% across 100:1
0.1% across 120:1
0.001% across 100:1
0.1% across 120:1
Speed control bandwidth
(radians per second)
20
250
190
50
190
50
Slip compensation
Standard
Standard
Standard
Standard
Droop
—
Standard
Standard
Standard
Inertia adaption
—
—
—
Standard
Phase lock loop
—
—
—
Standard
Torque regulation
—
± 2%, 2500 rad/sec
± 5%, 600 rad/sec
± 2%, 2500 rad/sec
± 5%, 600 rad/sec
± 2%, 2500 rad/sec
± 5%, 600 rad/sec
Features
Flying start
Standard
Standard
(4)
Standard
(5)
Standard
Bus regulator
Standard
Standard
Standard
S-curve
Standard
Standard
Standard
Standard
Drive overload protection
Standard
Standard
Standard
Advanced diagnostics
Standard
Standard
Standard
Standard
(1) Frames 0…6 only.
(2) With encoder.
(3) Without encoder.
(4) Advanced.