Data Transfer File Instructions
Chapter 12
1218
Figure 12.16
FILETOWORD MOVE Example Rung
FILE-TO-WORD MOVE
COUNTER ADDR: 200
POSITION: 005
FILE LENGTH: 010
FILE A: 474- 505
WORD ADDRESS: 400
200
(DN)
15
This output instruction transfers a duplicate of the value in a specified data
table word W (Figure 12.17) into a word in file R that is pointed to by the
counter accumulated value.
Instruction overview:
Output instruction
Key sequence: [FILE] 11
Requires 4 words of user program
Counter must be externally indexed by program
12.4
WordtoFile Move