68
Rockwell Automation Publication 440R-UM013E-EN-P - March 2017
Chapter 11
Troubleshooting
2. Check the voltage at each of the inputs with the device contacts closed,
. The values must be very close to the values
measured at terminals S11 and S21.
a. If both channels are closed, a voltmeter must read about 19V and the
IN indicator is green. The voltage levels are approximately the same
on Channel 1 (S12) and Channel 2 (S22) because the pulse testing
waveforms are similar on both channels.
b. If only one input is above the turn ON voltage level, then the IN
indicator is red.
c. Try cycling the input device.
d. If the contacts of the safety device do not operate consistently, the
safety device must be replaced.
Figure 61 - Check the CI Safety Inputs with the Device Contacts Closed
3. If a significant difference in voltage levels exists, see
Long Wire — Resistance Effect on page 72
To find where the voltage drop is occurring, you have to trace the wiring
of the circuit that is not achieving at least 11V as measured by an
oscilloscope.
Check DI, DIS, and SI Safety Relays
DI, DIS, and SI safety relays can also be checked in a similar fashion. The
voltage of Channel 1 is lower (about 14V) than Channel 2 (about 18V). The
reason for the difference in voltage levels is due to the difference in the pulse
). S11 is effectively OFF longer
than S21.
Pulse Testing
Outputs
S11
S21
S12
19
19
S22
A2
Volts
DMM
Volts
DMM
Summary of Contents for Guardmaster
Page 12: ...12 Rockwell Automation Publication440R UM013E EN P March 2017 Chapter 1 Overview Notes...
Page 16: ...16 Rockwell Automation Publication440R UM013E EN P March 2017 Chapter 2 Installation Notes...
Page 40: ...40 Rockwell Automation Publication440R UM013E EN P March 2017 Chapter 4 Configuration Notes...
Page 99: ......