Switch Adjustment
These safety relays have multi-position switches on their front face. Use a small
screwdriver to set the switches to the desired setting.
Figure 25 - Configuration Switch Adjustment
CI and SI safety relays have a three-position Reset switch. This switch
determines whether the relay uses a monitored manual reset or an automatic/
manual switch (see
).
Table 5 - CI and SI Logic Switch
DI and DIS Safety Relays
The DI and DIS safety relays have a 10-position switch and use only the first
, this switch configures the relay for its reset
and logic functionality.
Table 6 - DI and DIS Logic Switch
Example 1:
Logic setting 1 or 5: If any of the inputs (IN1, IN2, or L12) are
ON, then the safety relay refers to the reset logic.
Example 2:
Logic setting 4 or 8: If all three of the inputs (IN1, IN2, and L12)
are ON, then the safety relay refers to the reset logic.
TIP
Make note of the mechanical stop location.
IMPORTANT
Adjust the switches gently and do not turn past the mechanical stops.
Position
Function
0
Start configuration
MM
Monitored manual reset
AM
Automatic/manual reset
Position
Reset
Function
0
Not applicable
Start configuration
1
Monitored Manual
(IN1 OR IN2) OR L12
2
(IN1 AND IN2) OR L12
3
(IN1 OR IN2) AND L12
4
(IN1 AND IN2) AND L12
5
Automatic/Manual
(IN1 OR IN2) OR L12
6
(IN1 AND IN2) OR L12
7
(IN1 OR IN2) AND L12
8
(IN1 AND IN2) AND L12
0
Mechanical
Stops
Screwdriver
Slot
Summary of Contents for Guardmaster
Page 12: ...12 Rockwell Automation Publication440R UM013E EN P March 2017 Chapter 1 Overview Notes...
Page 16: ...16 Rockwell Automation Publication440R UM013E EN P March 2017 Chapter 2 Installation Notes...
Page 40: ...40 Rockwell Automation Publication440R UM013E EN P March 2017 Chapter 4 Configuration Notes...
Page 99: ......