42
Rockwell Automation Publication 1756-RM010C-EN-P - August 2018
Chapter 2
Replacement Considerations
b. Select the Ethernet module catalog number and click Next.
c. Browse to the module in the secondary chassis and select it.
d. Click OK.
e. Select the firmware revision to update to and click Next.
f. Click Finish.
The firmware begins to update. When the update is complete, the
Update status dialog box indicates completion.
Wait for the update to complete.
g. After the update completes, connect the Ethernet cable to the
secondary Ethernet module, and wait for communication to resume
on the network.
16. Repeat steps
10
…
15
for all EtherNet/IP modules in the secondary
chassis.
Complete these steps to verify module compatibility and synchronization.
1. At the Synchronization status tab, verify that the Synchronization Status
tab indicates that the modules are fully compatible.
Secondary
Chassis