10. Make a note of the Port Configuration of the secondary Ethernet
module.
• IP address
• Network Mask
• Gateway address
11. Disconnect the Ethernet cables from the secondary Ethernet module.
12. Turn off power to the secondary chassis.
13. Remove the EtherNet/IP module from the secondary chassis.
14. Set the switches on the new EtherNet/IP module to 888, insert the
module in the secondary chassis, and apply power to the chassis.
a. After the reset is complete, turn power off to the secondary chassis,
remove the module from the secondary chassis.
b. Set the switches to the same settings as on the module that was
removed.
c. Reinsert the module into the secondary chassis, reattach the cable,
and apply power to the secondary chassis.
d. To support bridging across the backplane (or via the USB port),
configure the Port Configuration of the secondary module to match
the Port Configuration of the primary module.
15. If you have not already done so, update the firmware of the new
EtherNet/IP module.
a. Launch ControlFLASH software, and click Next.