24
Rockwell Automation Publication 1756-RM010C-EN-P - August 2018
Chapter 1
Update Considerations
Complete the steps in this table to update your redundancy system from one
redundancy system revision to another redundancy revision while your process
continues to run.
Prepare the Redundant Chassis for the Firmware Update
Complete these steps to prepare both the primary and secondary redundant
chassis for redundancy firmware updates.
1. Set the mode switch of the primary and secondary controllers to REM.
If the redundant controllers in both chassis of the redundant chassis pair
are not in Remote Program (REM) mode, the redundancy firmware
update cannot be completed.
2. Open RSLinx Classic software and browse to the redundancy module.
3. To open the RMCT, right-click the redundancy module and choose
Module Configuration.
4. Click the Configuration tab in the RMCT.
Task
Page
Prepare the Redundant Chassis for the Firmware Update
24
Update the Redundancy Module Firmware in the Primary Chassis
26
Update Redundancy Module Firmware and Other Module Firmware in the Secondary Chassis
28
Lock the System and Initiate a Switchover to Update
30
Update the New Secondary Chassis Firmware
32
Synchronize the Redundant Chassis
34