Safety Instructions
The following tables list the safety application instructions that are certified for
use in SIL 2 or SIL 3 applications.
ATTENTION:
These safety instructions are the only instructions that can be
used in the safety tasks in SIL 2 or SIL 3 applications.
Table 5 - General Safety-application Instructions
Mnemonic
Name
Purpose
CROUT
Configurable Redundant Output
Controls and monitors redundant outputs.
DCA
Dual Channel Input - Analog (integer
version)
Monitors two analog values for deviation and range tolerance.
DCAF
Dual Channel Input - Analog (floating
point version)
DCS
Dual Channel Input - Stop
Monitors dual-input safety devices whose main purpose is to provide a stop function, such as an
E-stop, light curtain, or gate switch.
DCST
Dual Channel Input - Stop With Test
Monitors dual-input safety devices whose main purpose is to provide a stop function, such as an
E-stop, light curtain, or gate switch. It includes the added capability to initiate a functional test of the stop device.
DCSTL
Dual Channel Input - Stop With Test
and Lock
Monitors dual-input safety devices whose main purpose is to provide a stop function, such as an
E-stop, light curtain, or gate switch. It includes the added capability to initiate a functional test of the stop device. It
can monitor a feedback signal from a safety device and issue a lock request to a safety device.
DCSTM
Dual Channel Input - Stop With Test
and Mute
Monitors dual-input safety devices whose main purpose is to provide a stop function, such as an
E-stop, light curtain, or gate switch. It includes the added capability to initiate a functional test of the stop device and
the ability to mute the safety device.
DCM
Dual Channel Input - Monitor
Monitors dual-input safety devices.
DCSRT
Dual Channel Input - Start
Energizes dual-input safety devices whose main function is to start a machine safely, for example an enable pendant.
SMAT
Safety Mat
Indicates whether the safety mat is occupied.
THRSe
Two-Hand Run Station – Enhanced
Monitors two diverse safety inputs, one from a right-hand push button and one from a left-hand push button, to
control one output. Features configurable channel-to-channel discrepancy time and enhanced capability for
bypassing a two-hand run station.
TSAM
Two Sensor Asymmetrical Muting
Automatically disables the protective function of a light curtain temporarily, by using two muting sensors that are
arranged asymmetrically.
TSSM
Two Sensor Symmetrical Muting
Automatically disables the protective function of a light curtain temporarily, by using two muting sensors that are
arranged symmetrically.
FSBM
Four Sensor Bi-directional Muting
Automatically disables the protective function of a light curtain temporarily, by using four sensors that are arranged
sequentially before and after the sensing field of the light curtain.