Publication 2100-IN012B-EN-P - April 2005
Final Checklist Before Energizing
3-7
Table 3.B Spacing Requirements within Motor Control Center Units
(1)
,
(2)
,
(3)
Voltage
involved
Minimum spacing, inch (mm)
Between uninsulated live parts of opposite
polarity and between an uninsulated live
part and an exposed or uninsulated dead
metal part other than the enclosure
Between uninsulated live
parts and the walls of a metal
enclosure
(3)
, including
fittings for conduit or
armored cable
Through air
Over surface
Shortest distance
125 or less
1/8” (3.2mm)
(2)
1/4” (6.4mm)
1/2” (12.7mm)
126 – 250
1/4” (6.4mm)
3/8” (9.5mm)
1/2” (12.7mm)
251 – 600
3/8” (9.5mm)
1/2” (12.7mm)
1/2” (12.7mm)
(1)
Reference Underwriters Laboratories, Inc. Standards for Motor Control Centers, UL 845, Tables 16.1 and 16.3.
(2)
The spacing between wiring terminals of opposite polarity shall not be less than 1/4” (6.4 mm) if the terminals are in the same
plane.
(3)
The enclosure refers to the section enclosure.
NOTE –
A metal piece attached to the enclosure is considered a part of the enclosure for the purpose of this note if deformation of the
enclosure is likely to reduce the spacing between the metal piece and a live part.
Summary of Contents for CENTERLINE
Page 1: ...CENTERLINE Low Voltage Motor Control Centers Instruction Manual ...
Page 6: ...Publication 2100 IN012B EN P April 2005 iv ...
Page 8: ...Publication 2100 IN012B EN P April 2005 vi ...
Page 30: ...Publication 2100 IN012B EN P April 2005 2 10 Installation Procedures ...
Page 42: ...Publication 2100 IN012B EN P April 2005 3 12 Final Checklist Before Energizing ...
Page 48: ...Publication 2100 IN012B EN P April 2005 4 6 Installing Conduit and Cable ...
Page 56: ...Publication 2100 IN012B EN P April 2005 5 8 Installing and Removing Plug In Units ...
Page 68: ...Publication 2100 IN012B EN P April 2005 7 10 Operator Handle and Unit Interlock ...
Page 76: ...Publication 2100 IN012B EN P April 2005 9 6 Maintenance ...
Page 78: ...Publication 2100 IN012B EN P April 2005 10 2 Maintenance After Fault Condition ...
Page 80: ...Publication 2100 IN012B EN P April 2005 11 2 Renewal Parts ...
Page 85: ...Publication 2100 IN012B EN P April 2005 Parts Illustrations 12 5 Notes ...
Page 86: ...Publication 2100 IN012B EN P April 2005 12 6 Parts Illustrations Notes ...