1
Publication 2100-IN012B-EN-P—April 2005
Chapter
2
Installation Procedures
Location Planning
When planning the location for your CENTERLINE Motor Control Center,
consider the following:
•
Conduits
•
Busways
•
Overall height of installation area
•
Alignment with other equipment
•
Future needs
•
Ambient temperature
The area must be level and the environment must be compatible with the
NEMA enclosure rating of the equipment.
Height Considerations
If the motor control center is equipped with optional external mounting
channels or is mounted on a pad, the height from the floor to the center of the
top handles must be checked for compliance with 2005 NEC 404.8(A) and UL
Standard 845. If the distances from the floor to the center of the highest
handle is greater then 6’7” (2000 mm) a unit operating handle extender should
be added (catalog number 2100H-NE1). See Figure 2.1.
Summary of Contents for CENTERLINE
Page 1: ...CENTERLINE Low Voltage Motor Control Centers Instruction Manual ...
Page 6: ...Publication 2100 IN012B EN P April 2005 iv ...
Page 8: ...Publication 2100 IN012B EN P April 2005 vi ...
Page 30: ...Publication 2100 IN012B EN P April 2005 2 10 Installation Procedures ...
Page 42: ...Publication 2100 IN012B EN P April 2005 3 12 Final Checklist Before Energizing ...
Page 48: ...Publication 2100 IN012B EN P April 2005 4 6 Installing Conduit and Cable ...
Page 56: ...Publication 2100 IN012B EN P April 2005 5 8 Installing and Removing Plug In Units ...
Page 68: ...Publication 2100 IN012B EN P April 2005 7 10 Operator Handle and Unit Interlock ...
Page 76: ...Publication 2100 IN012B EN P April 2005 9 6 Maintenance ...
Page 78: ...Publication 2100 IN012B EN P April 2005 10 2 Maintenance After Fault Condition ...
Page 80: ...Publication 2100 IN012B EN P April 2005 11 2 Renewal Parts ...
Page 85: ...Publication 2100 IN012B EN P April 2005 Parts Illustrations 12 5 Notes ...
Page 86: ...Publication 2100 IN012B EN P April 2005 12 6 Parts Illustrations Notes ...