Rockwell Automation Publication ICSTT-RM446N-EN-P - April 2018
Chapter 4
AADvance Functional Safety System Implementation
Digital Input Field Loop Circuits
Recommended Field Loop Circuits
This section contains recommended field loop circuits for line monitoring
digital inputs used in Emergency Shutdown or Fire & Gas applications.
Field Loop Circuit for Digital Input
Field Loop Circuit for Line Monitored Digital Input for Emergency Shutdown Systems (ESD)
The suggested values for R1 and R2 are as follows:
R1 = 15K
1%, 1W (maximum power dissipated is 47mW at 26.4V)
R2 = 3K9
1%, 1W (maximum power dissipated is 182mW at 26.4V)