7–7
Communicating with an SLC on a DH-485 Network
Publication 2755-6.8
This section describes how to configure the SLC 5/04, which is
different than the 5/03.
•
Using APS and an RS-232 connection, establish an online
connection the Channel 0 port of the SLC 5/04.
•
When online, change to DH485 protocol and do a WHO ACTIVE
to view the nodes on the network.
For complete details on configuring the SLC 5/04 or 5/03 processors,
refer to the Advanced Programming Software manuals.
SLC 5/04 Configuration
1. Establish communication with the Channel 0 port of the SLC
5/04 using the 1747-CP3/A RS-232 cable.
Default
On line configuration
DF1 Full
F7 1200
Enter (twice)
On line (in RS-232)
2. Verify that you are online in “REM RUN”.
Change configuration driver F2 – PIC
Baud Rate 19,200
Max Node 3
F7 Utility
F5 Channel 0 (Master Mode)
Power down and up
Configuring the SLC
Controller