62
Rockwell Automation Publication 23PFC-TG001A-EN-P - March 2018
Chapter 3
Frame A Field Controller Part Replacement Procedures
Install the AC Current Transducers
Install the AC current transducers in reverse order of removal.
For AC current transducers that must be wound with wire leads:
• Wind the wire leads around the new AC current transducers the exact
number of times and in the same position as the wires on the AC current
transducers that were removed from the power traces board.
• Crimp the connection lugs onto the wire leads before they are secured to
the power traces board.
Wrap wire around AC
Current Transducer
Crimp connection lug
onto wire ends