48
Rockwell Automation Publication 23PFC-TG001A-EN-P - March 2018
Chapter 3
Frame A Field Controller Part Replacement Procedures
Control EMI Shield and
Control Circuit Board
Replacement
Remove the Control EMI Shield and Control Circuit Board
You must remove the control EMI shield that holds the control board to access
other components within the device.
1. Read the General Safety Precautions on page
2. Remove power from the device (see page
3. Remove the protective covers (see page
).
4. Carefully disconnect the cables from connectors XA and XR on the
control board.
5. Remove the plug-in I/O terminal blocks with the wiring kept in place (if
used).
=
4
5
Control board shown with
communication adapter and
optional boards removed.