92
Rockwell Automation Publication 193-UM014C-EN-P - August 2016
Appendix A
Specifications
Table 27 - Electromagnetic Compatibility
Table 28 - EtherNet/IP Communication
Table 29 - Standards & Certifications
Electromagnetic Compatibility
Electrostatic Discharge Immunity
Test Level
Performance Criteria
8 kV Air Discharge
4 kV Contact Discharge
B
(1)
(2)
(1) Performance Criteria B requires the DUT (device under test) not to experience degradation or loss of performance.
(2) Environment 2 - Heavy Industrial.
RF Immunity
Test Level
Performance Criteria
10V/m: 80 MHz…1 GHz
3V/m: 1.4 GHz…2 GHz
1V/m: 2.0 GHz…2.7 GHz
B
Electrical Fast Transient/Burst Immunity
Test Level
Performance Criteria
2 kV (Power Protective Earth)
1 kV (control bus cable)
B
Surge Immunity
Test Level
Performance Criteria
1 kV L-L (bus cable)
B
Radiated Emissions
Class A
Conducted Emissions
Class A
ATTENTION:
This is a class A product. In domestic environment, this product
may cause radio interference, in which case you may be required to take
adequate measures.
EtherNet/IP Communication
Total Connections Supported
TCP
CIP
150
47
Total CIP Unconnected Messages Supported
128
CIP Class 1 Connection Consumed
1
Packet Rates (packets/second)
I/O
HIM/MSG
500
500
Media Support
Twisted Pair
Fiber
Yes
No
Speed Duplex (Half/Full)
10/100
Duplicate IP Detection
Yes
Standards and Certifications
UL 508
CSA 22.2, No. 14
EN 60947-4-1
Summary of Contents for 193-DNENCAT
Page 6: ...6 Rockwell Automation Publication 193 UM014C EN P August 2016 Table of Contents Notes...
Page 8: ...8 Rockwell Automation Publication 193 UM014C EN P August 2016 Summary of Changes Notes...
Page 10: ...10 Rockwell Automation Publication 193 UM014C EN P August 2016 Preface Notes...
Page 80: ...80 Rockwell Automation Publication 193 UM014C EN P August 2016 Chapter 8 Email Text Notes...
Page 111: ......