72
Rockwell Automation Publication 193-UM014C-EN-P - August 2016
Chapter 7
Automation Controller Communication
2. Set up the MSG instruction in the Configuration tab to read the list of
attributes (Parameters Group) by configuring the following fields:
• Message Type: CIP Generic
• Service Type: Custom
• Service Code: 0x03 (hex)
• Class: 0x375 (hex)
• Instance: 1 (dec)
• Attribute: 0x00 (hex)
• Source Element: MSG_Read_Request [0]
• Source Length: 14 (bytes)
• Destination: MSG_Read_Data
3. Set up the communications path in the Communications tab to read the
data from the E3 Plus Electronic Overload Relay located at Node 6 by
configuring the communication path as “MotorStarter, 3, 6”.
NOTE:
Motor Starter — the name of the EtherNet/IP communication auxiliary module
3 — the port number of the DeviceNet Scanner of the EtherNet/IP communication auxiliary module.
6 — the node address of the E3 Plus Electronic Overload Relay.