84
Rockwell Automation Publication 193-UM014C-EN-P - August 2016
Chapter 9
Device Parameters
Table 19 - Parameter 9 — Device Keys
Table 20 - Parameter 10 — Scanlist Config
Table 21 - Parameter 11 — ADR Record
Table 22 - Parameter 12 — ADR Enable
Table 23 - Parameter 13 — DNet IO RPI
Table 24 - Parameter 14 — DNet IO Inhibit
Description
Access Rule
Data Type
Units
Value
Min.
Max. Default
Determines how electronic
keying is performed.
Get/Set
USIN T
—
0
63
7
Bit
0 Device Type
2 Product Code
4 Minor Revision
1 Vendor
3 Major Revision
5 Minor of Higher
Description
Access Rule
Data Type Units
Value
Min.
Max. Default
Triggers the building of a new
DeviceNet scan list.
0 = Ready
1 = Build Scan List
Get/Set
BOOL
—
0
1
0
Description
Access Rule
Data Type Units
Value
Min.
Max. Default
Triggers the recording of configuration
parameters from devices in the
DeviceNet scan list to be used for
Automatic Device Replacement.
0 = Ready
1 = Record Parameters
Get/Set
BOOL
—
0
1
0
Description
Access Rule
Data Type Units
Value
Min.
Max. Default
Enables Automatic Device Replacement.
0 = Disable
1 = Enable
Get/Set
BOOL
—
0
1
0
Description
Access Rule
Data Type Units
Value
Min.
Max. Default
Defines the requested packet interval
rate in milliseconds used on DeviceNet
Polled I/O messaging.
Get/Set
WORD
ms
2
1000
75
Description
Access Rule
Data Type
Units
Value
Min.
Max. Default
Defines the inhibit time in milliseconds
used on DeviceNet Change of State
(COS) I/O messaging.
Get
WORD
ms
2
1000
1
Summary of Contents for 193-DNENCAT
Page 6: ...6 Rockwell Automation Publication 193 UM014C EN P August 2016 Table of Contents Notes...
Page 8: ...8 Rockwell Automation Publication 193 UM014C EN P August 2016 Summary of Changes Notes...
Page 10: ...10 Rockwell Automation Publication 193 UM014C EN P August 2016 Preface Notes...
Page 80: ...80 Rockwell Automation Publication 193 UM014C EN P August 2016 Chapter 8 Email Text Notes...
Page 111: ......